MONITORING SOLUTION ENERGY
SENSeOR AMS01 User Manual 16/29
www.senseor.com
1.7.2 RELAY OUTPUT
Output relay connections are recommended to be at a minimum of 16 AWG and tin-coated, with a soft
drawn copper of ASTM B8, Class B stranding, 300V rated. Insulation shall be EP (Ethylene Propylene)
or EPCP (Ethylene Propylene Chlorosulfonated Polyethylene compound).
1.7.3 INTERNAL BATTERY
SENSeOR reader has an internal 3VDC non rechargeable battery to keep the UTC date and the time in
case of power down.
It can be replaced only by authorized person using the following or an equivalent reference:
3V Lithium battery CR2032
WARNING
THERE IS A RISK OF EXPLOSION IF THE BATTERY IS REPLACED BY AN INCORRECT TYPE.
BE CAREFUL OF USED BATTERY IN ACCORDANCE WITH YOUR REGIONAL LEGAL INSTRUCTIONS.