EasyManuals Logo

Wilo Control SC2.0-Booster User Manual

Wilo Control SC2.0-Booster
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
en
Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09 11
p-v
Control mode p-c, Vario mode
Set Vario mode: Control settings→Control→BLP selection diagram
An electronic pressure transmitter supplies the actual pressure value as a 4…20mA or
0…20mA current signal. Then the controller maintains the system pressure at a constant
level by means of the comparison of the setpoint/actual value.
Set the measurement range of the pressure sensor: System→Sensors→Discharge side
measurement range
Set sensor type: System→Sensors→Discharge side sensor type
Set reference setpoint (1): Control settings→Setpoints→Setpoints 1
If there is no “external off” message and no fault, and the drives as well as the automatic
system are activated, the base-load pump starts when the activation threshold (2) is fallen
below.
Control setting→Standby→Drives, automatic
Set the activation threshold individually for each pump: Control setting→Setpoint-
s→Switching on and off of BLP
Fig.5: Starting the load-sensitive speed-controlled base-load pump
If the power requirement can no longer be met by this pump with the set speed, another
pump starts when the power falls below the reference setpoint (1) and takes over the
speed control.
Set speed: System→Frequency converter→Limits
Fig.6: Starting the second pump

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Control SC2.0-Booster and is the answer not in the manual?

Wilo Control SC2.0-Booster Specifications

General IconGeneral
BrandWilo
ModelControl SC2.0-Booster
CategoryExtender
LanguageEnglish