56 Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09
Holding register
(protocol)
Name Data type Scaling and
unit
Elements Access* Supple-
mentary
40003
(2)
Control device type ENUM  0. SC
 1. SC...FC
 2. SCe
 3. CC
 4. CC...FC
 5. CCe
 6. SCe NWB
 7. CCe NWB
 8. EC
 9. ECe
10. ECe NWB
R 31,000
40008–40009
(7–8)
Control device data ID UINT32 R 31,000
40014
(13)
BusCommand timer ENUM 0.-
1. Off
2. Set
3. Active
4. Reset
5. Manual
RW 31,000
40015
(14)
Drives on/off BOOL RW 31,000
40026
(25)
Actual value INT16 0.1bar
0.1m
0.1K
0.1°C
1cm
1min
0.1h
0.1psi
R 31,000
40027
(26)
Current setpoint INT16 0.1bar
0.1m
0.1K
0.1°C
1/day
1/month
0.1psi
RW
R (dp-v)
R (dT-v)
31,000
40028
(27)
Number of pumps UINT16 R 31,000
40029
(28)
Maximum number of active
pumps
UINT16 R 31,000