en
Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09 57
Holding register
(protocol)
Name Data type Scaling and
unit
Elements Access* Supple-
mentary
40033
(32)
Pump status 1 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31,000
40034
(33)
Pump status 2 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31,000
40035
(34)
Pump status 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31,000
40036
(35)
Pump status 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31,000
40041
(40)
Pump mode 1 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40042
(41)
Pump mode 2 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40043
(42)
Pump mode 3 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40044
(43)
Pump mode 4 ENUM 0. Off
1. Manu
2. Auto
RW 31,000
40062
(61)
General status BITMAP 0: SBM
1: SSM
R 31,000
40068
(67)
Setpoint 1 UINT16 0.1bar
0.1m
0.1 K
0.1 °C
0.1 psi
RW 31,000