58 Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09
Holding register
(protocol)
Name Data type Scaling and
unit
Elements Access* Supple-
mentary
40069
(68)
Setpoint 2 UINT16 0.1bar
0.1m
0.1 K
0.1 °C
0.1 psi
RW 31,000
40074
(73)
Application ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31,101
40075
(74)
External setpoint INT16 0.1bar
0.1m
0.1 K
0.1 °C
0.1 psi
R 31,000
40076
(75)
Activate external
setpoint
BOOL RW 31,000
40077–40078
(76–77)
Number of switching-on pro-
cedures of the system
UINT32 R 31,000
40079–40080
(78–79)
Control device data: Operating
hours
UINT32 1h R 31,000
40081–40082
(80–81)
Total switching cycles of pump
1
UINT32 R 31,000
40083–40084
(82–83)
Total switching cycles of pump
2
UINT32 R 31,000
40085–40086
(84–85)
Total switching cycles of pump
3
UINT32 R 31,000
40087–40088
(86–87)
Total switching cycles of pump
4
UINT32 R 31,000
40097–40098
(96–97)
Total operating hours of pump
1
UINT32 1h R 31,000
40099–40100
(98–99)
Total operating hours of pump
2
UINT32 1h R 31,000
40101–40102
(100–101)
Total operating hours of pump
3
UINT32 1h R 31,000
40103–40104
(102–103)
Total operating hours of pump
4
UINT32 1h R 31,000