22 Installation and operating instructions • Wilo-Yonos MAXO/-D/-Z • Ed.01/2022-08
• The use of securing elements (e.g. spring lock washers) can result in leakages at the flange connection. They
are therefore not permissible. Use the washers supplied (scope of delivery) between screw heads/nut heads
and the combination flange!
• The permissible tightening torques listed in the table below must not be exceeded, even if screws of higher
strength (≥4.6) are used, since splintering may otherwise occur at the edges of the long holes. This may
cause the screws to lose their prestress and leakage can occur in the flange connection. Risk of scalding!
• Use screws of sufficient length. The screw thread must project by at least one pitch of screw thread from
the screw nut.
• Perform leakage test at maximum permissible operating pressure!
Screws and tightening torques
Flange-end pump PN6
DN32 DN40 DN50
Screw diameter M12 M12 M12
Strength class ≥4.6 ≥4.6 ≥4.6
Tightening torque 40Nm 40Nm 40Nm
Screw length ≥55mm ≥55mm ≥60mm
DN65 DN80 DN100
Screw diameter M12 M16 M16
Strength class ≥4.6 ≥4.6 ≥4.6
Tightening torque 40Nm 95Nm 95Nm
Screw length ≥60mm ≥70mm ≥70mm
Flange-end pump PN10
DN32 DN40 DN50
Screw diameter M16 M16 M16
Strength class ≥4.6 ≥4.6 ≥4.6
Tightening torque 95Nm 95Nm 95Nm
Screw length ≥60mm ≥60mm ≥65mm
DN65 DN80 DN100
Screw diameter M16 M16 M16
Strength class ≥4.6 ≥4.6 ≥4.6
Tightening torque 95Nm 95Nm 95Nm
Screw length ≥65mm ≥70mm ≥70mm
Installation steps
1. Close the shut-off valves in front of and behind the pump (Fig.III).