EasyManua.ls Logo

Wilo Yonos MAXO - Min. Inlet Pressure

Wilo Yonos MAXO
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en
Installation and operating instructions • Wilo-Yonos MAXO/-D/-Z • Ed.01/2022-08 17
Specification Value
Emissions sound-pressure level < 52dB(A)
Energy efficiency index (EEI) See rating plate
Temperature class TF110 (see IEC60335-2-51)
Pollution degree 2 (IEC60664-1)
Max. permissible operating pressure PN6/10
For further instructions see rating plate and catalogue.
Technical data Yonos MAXO-Z
Specification Value
Permissible fluid temperature 0°C...+80°C (for short periods (2h): +110°C)
Permissible ambient temperature 0°C...+40°C
Maximum relative humidity ≤ 95%
Mains voltage 1~ 230V +/-10% 50/60Hz
Residual current ∆I ≤3.5mA
Electromagnetic compatibility Interference emission in acc. with:
EN61800-3:2004+A1:2012/residential environment
(C1)
Interference immunity in acc. with:
EN61800-3:2004+A1:2012/industrial environment
(C2)
Emissions sound-pressure level < 52dB(A)
Energy efficiency index (EEI) See rating plate
Temperature class TF80 (see IEC60335-2-51)
Pollution degree 2 (IEC60664-1)
Max. permissible operating pressure PN6/10
For further instructions see rating plate and catalogue.
5.4 Min. inlet pressure
Nominal diameter Fluid temperature
-20°C to +50°C
0°C to +50°C
1)
up to +95°C up to +110°C
G 1½ 0.3bar 1.0bar 1.6bar
G 2 0.3bar 1.0bar 1.6bar
DN32 0.3bar 1.0bar 1.6bar
DN40 0.5bar 1.2bar 1.8bar

Related product manuals