EasyManua.ls Logo

Wolf CGB-100 - 18. Commissioning; Setting the BUS Address; Commissioning Checklist; Energy Saving Advice; BUS Address Setting

Wolf CGB-100
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
333062555_201804
Energysavings
-Instructthecustomeraboutenergysavingoptions.
-Referthecustomertothesection"Informationforen-
ergyefcientoperation"intheoperatinginstructions.
18.Commissioning/settingtheBUS
address
Only qualied personnel must carry out the
commissioningandinitialstart-upoftheboiler
andinstructionoftheuser.
- Check that all ue gas accessories have been correctly
installed
- Opentheshut-offvalvesintheowandreturn
- Open the gas shut-off valve
- Switch on the system ON/OFF switch on the control unit
-Check the ignition and the regular ame structure of the
burner
- The illuminated ring shows a yellow colour, if the boiler starts
correctly
- Check the condensate drain
- Familiarise customers with the operation of the boiler with
reference to the operating instructions and advise them of
therequiredwatertreatmentforllandtop-upwater
- Complete the commissioning report and hand over the
instructions to the customer.
Fig.: Control unit overview
ON/OFF
ON/OFF
switch
ThermometerReset button
Illuminated ring
- Check the boilerand system for leaks;
Normaloperatingpressurewhensystemiscold
1.5-2.0bar;preventwaterleaks
- Checkthelocationandseatingofttedcom-
ponents
- Checkallconnectionsandcomponentunions
forleaks.
- Ifleaktightnesscannotbeensured,thereis
ariskofwaterdamage.
Note
BUSaddresssetting
Whenoperatingseveralboilers(numberofboilers>1)inconjunctionwithacascademodule,settheBUSaddressofeachboiler
in accordance with the table below.
BUS address setting:
Holddowntheresetbutton;after5seconds,thecorrespondingashingcodewillbedisplayed(seetable).Selectthecorresponding
addresswiththeDHWtemperaturerotaryselector.Thenreleasetheresetbuttonagain.
Busaddress RotaryselectorpositionDHW Illuminatedringdisplay
1 1 ashingred
2 2 ashingyellow
3 3 ashingyellow/red
4 4 ashingyellow/green
5 5 ashinggreen/red
0 6 ashinggreen(factorysetting)

Other manuals for Wolf CGB-100

Related product manuals