Specification
Ratedoutputat 80/60°C
Ratedoutput at 50/30 DC
Ratedthermal load
Lowestoutput (modulating)at 80/60
Lowestoutput (modulating)at 50/30
Lowestthermal load (modulating)
kW
kW
kW
kW
kW
kW
37.2
40.5
37.9
11.2
12.1
11.4
55.4
60.6
57.2
21.9
23.6
22.3
Gasconnection value:
NaturalgasE/H(Hi=9.5 kWh/m3=34.2MJ/m3)m3/h
Natural gas LL(Hi=8.6 kWh/m3=31.0MJ/m3)m3/h
LPG(Hi= 12.8kWh/kg=46.1MJ/kg) kg/h
Gassupplypressure:
Naturalgas
LPG
4.0
4.4
3.0
6.0
6.7
mbar
mbar
17-25
25-45
17-25
Permissiblesensor temperatures
Fluegas massflow rate
Fluegas temperature 80/60 - 50/30
Availablegas fan draught
Fluegas value group accordingto DVGWG635
DC
g/s
DC
Pa
95
17.3
67- 43
130
G52
95
26.7
80-50
185
G52
* notapplicabletoAustria/Switzerland
36