Manual 37942A DTSC-200A - ATS Controller - Application
Page 10/21 © Woodward
Example Application: External Permit Closed Transition
In some ATS applications the customer may want to use an additional “Sync-check relay” in combination with
the DTSC-200A for highest system security. Only if the external sync-check relay sends a “Synchronism detect-
ed” signal to the DTSC-200A, then the in-phase monitor in the DTSC-200A shall be activated.
The “Enable closed transition” LogicsManager is the ideal function to carry out this functionality.
Figure 2-5: Example application external permit closed transition
Setup:
Parameter “Ext. permit for cld. trans.” must be set to “On” to activate this feature
Parameter “Transfer switch type” must be configured to “Closed”
Wire the relay output of the external sync-check relay to a free discrete input on the DTSC-200A
Configure the LogicsManager for “Enable closed transition” in such a way, that the discrete input you
intend to use is setup here