Commissioning
6720813171 (2015/04) 39
Slowly open the gas valve by pushing on the gas valve and turning it
¼ rotation in an anticlockwise direction. The gas valve is open when
it is in the vertical position.
Fig. 79 Open the gas valve
Switch off the power supply to the heating system.
Fig. 80 Switch off the power supply to the heating system
Check the new pipe section up to and including its connection (i.e.
direct sealing location) to the gas fitting for leaks, using a foaming
product. The maximum test pressure allowed at the gas valve inlet is
150 mbar.
10.2.2 Bleeding the gas flow pipe
Close the gas valve.
Fig. 81 Closing the gas valve
Open the screw plug on the testing nipple of the gas supply pressure
and for purging [1] by 2 turns and install a hose.
Slowly open the gas valve by pushing on the gas valve and turning it
anticlockwise through ¼ rotation ( fig. 85, page 58). The gas valve
is open when it is in the vertical position.
Purge the gas supply into a well ventilated area.
Close the gas shut-off valve when no more air is present (fig. 87).
Remove the hose and tighten the screw plug on the testing nipple
again.
Fig. 82 Bleeding the gas flow pipe
10.2.3 Gas consumption test
Isolate all other appliances.
Set the boiler to full load.
Ensure that there is no modulating of the fan gas valve by operating
the test mode.
Carry out the gas consumption procedure as described in the latest
edition of the Essential Gas Safety book.
6 720 648 726-079.1TD
ON
OFF
6 720 648 726-080.1TD
6 720 648 726-081.1TD
NOTICE:
Test the tightness of the measuring nipple(s) used.
GB162-50/65
GB162-80/100
6720813171-2.1TD