EasyManua.ls Logo

Worcester GREENSTAR 29

Worcester GREENSTAR 29
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 611 137 GB (03.02)
30
Converting the appliance to different gas types
B Turn the function control until the display shows 2.
(= max. rated heat output).
The display and the button will flash.
Fig. 43
B Measure the CO
2
level.
B Prise off the seal on the gas flow restrictor.
B Adjust the gas flow restrictor (63) to obtain the CO
2
level given in Table 14. Refer to fig. 44.
Fig. 44
B Turn the function control anti-clockwise until the dis-
play shows 1. (= min. rated heat output).
The display and the button will flash.
Fig. 45
B Measure the CO
2
level.
B Remove the seal from the gas valve adjusting
screw (64) and adjust the CO
2
level to the figure
given in Table 14 for min. rated heat output.
Fig. 46
B Recheck the levels at min. and max. rated heat output
and re-adjust if necessary.
B Turn the function control anti-clockwise as far as the
stop so that the display shows 0.
(= Normal operating mode).
The display and the button will flash.
B Press and hold the button until the display
shows [ ].
B Reset the temperature control and the function con-
trol to their original positions.
The display will revert to the boiler flow temperature.
B Remove testing probe from the flue gas testing
point (234) and refit sealing plug.
B Re-seal gas valve adjusting screw and gas flow
restrictor.
B Replace outer case and secure.
B Set room thermostat and thermostatic radiator valves
to the desired temperature.
Gas Type
CO
2
reading
at max.
rated heat
output
CO
2
reading
at min.
rated heat
output
Natural gas type
(G20)
9.2 % 8.8 %
LPG (G31)
(propane)
10.8 % 10.5 %
Table 14
6 720 611 137-20.1O
63
6 720 610 332-64.1R
6 720 611 137-21.1O
64
3928-74.1R

Table of Contents

Related product manuals