29
Greenstar regular boiler range
vertical fluing options
The Greenstar regular boiler range have the choice of
2 differently sized vertical RSF flue systems, 100mm and
125mm. Both systems have different maximum lengths.
Options 1 to 4 detail the permissible lengths.
Vertical RSF flue
Vertical balanced flue kit
Comprises:
1 x flue terminal assembly
1 x weather sealing collar
1 x fire stop spacer
1 x vertical adaptor
Part No. 7 719 002 430 (100mm dia.)
Part No. 7 719 002 431 (125mm dia.)
Flue diameter 100mm 125mm
Greenstar Ri series
Minimum flue length 1,090mm 1,365mm
Maximum flue length
(inc. adaptor) 6,400mm 15,000mm
Greenstar CDi Classic Regular series
Minimum flue length 1,140mm 1,365mm
Maximum flue length
(inc. adaptor)
30CDi Classic Regular 9,400mm 18,500mm
40CDi Classic Regular 7,500mm 16,000mm
*Dimensions when fitted
Components Part no. Description
7 719 002 430
100mm dia. vertical balanced
flue kit
7 716 191 083
100mm dia. extension flue kit
(960mm*)
7 716 191 133
100mm dia. short flue extension
(220mm*)
7 716 191 084 100mm dia. 90º bend
7 716 191 085 100mm dia. 45º bend
7 719 002 431
125mm dia. vertical balanced
flue kit
7 719 003 666
125mm dia. extension flue kit
(960mm*)
7 719 003 664 125mm dia. 90º bend
7 719 003 665 125mm dia. 45º bend
7 716 191 090 Flashing – flat roof
7 716 191 091 Flashing – pitched roof
Minimum
Components required
length (mm)
Greenstar Ri series
100mm 1,090 1
125mm 1,365 1
Greenstar 30CDi Classic Regular
100mm 1,090 1
125mm 1,365 1
Greenstar 40CDi Classic Regular
100mm 1,090 1
125mm 1,365 1
Note: The short flue extension (100mm dia.) may be used
as an alternative to the standard extension as required up
to the maximum flue lengths stated (7 716 191 133).
Note: The maximum flue length must be reduced by the
following amounts for each bend used.
Greenstar CDi Greenstar CDi
Greenstar Ri Classic Regular Classic Regular
– all size flues 60/100mm flues 80/125mm flues
45º bend 1m 0.75m 1m
90º bend 2m 1.5m 2m