Automatic
Generator Start
Owner’s Guide

Table of Contents

Questions and Answers

  • J
    james87Aug 18, 2025
    What to do if Xantrex Portable Generator exceeded max number of start tries?
    • C
      Charles MitchellAug 18, 2025
      If the Auto Gen Start has tried and failed to start the generator, and to prevent draining the start battery, it has suspended further start attempts, check the generator’s fuel level and start battery condition. Consult the generator manual and clear the fault on the System Control Panel screen to allow a retry.
  • B
    Brittany RichAug 20, 2025
    What to do if Xantrex Automatic Generator is unable to stop?
    • M
      Melissa SosaAug 21, 2025
      If the Auto Gen Start has lost contact with the generator or the generator did not stop after the Auto Gen Start sent it a stop signal, change the Auto Gen Start mode to Manual Off. If this fails to work, stop the generator with the external stop switch. Check the generator and return the Auto Gen Start to automatic mode to resume automatic starts and stops.
  • J
    joseph26Aug 23, 2025
    What to do if Xantrex Portable Generator was stopped by external sensor?
    • J
      Joshua JohnsonAug 23, 2025
      If an external sensor connected to the Auto Gen Start has stopped the generator and put the Auto Gen Start into Manual Off mode, clear the fault and reset the Auto Gen Start to the desired mode after the sensor connected to the external shutdown has deactivated.
  • C
    Craig LeeAug 26, 2025
    What to do if Xantrex Portable Generator was started by its switch?
    • A
      Amy MayAug 26, 2025
      If the generator was started, but not by the Auto Gen Start, check your generator and stop it using the switch or control panel on the generator.
  • R
    reginaobrienAug 28, 2025
    What to do if Xantrex Portable Generator stopped externally?
    • J
      jacqueline14Aug 28, 2025
      If the generator has stopped, but not by the Auto Gen Start because it may have run out of gas, or may have been shut off by a switch on the generator, check the generator’s fuel level and mechanical condition, then start the generator manually (using the switch or control panel on the generator) to clear the warning.
  • J
    James OrtizAug 30, 2025
    What to do if Xantrex Automatic Generator is unable to start?
    • J
      Jessica ElliottAug 30, 2025
      If the Auto Gen Start tried, but could not start the generator, no action is required. The Auto Gen Start will try to start the generator again until it reaches the maximum number of start tries.
  • D
    diana03Sep 1, 2025
    Why Xantrex Automatic Generator Portable Generator auto triggers not enabled?
    • K
      Kathy CarlsonSep 1, 2025
      If you are attempting to enter Automatic Mode without setting Auto triggers, acknowledge the warning and set a start and stop trigger.
  • D
    Derek PenningtonSep 3, 2025
    What to do if Xantrex Automatic Generator Portable Generator mismatched triggers?
    • R
      Ronald AndersonSep 3, 2025
      If you have set a stop trigger, but not a corresponding start trigger, acknowledge warning and set a start trigger.
  • N
    Nathan BarberSep 6, 2025
    What to do if Xantrex Automatic Generator max generator run time reached?
    • M
      Mario JohnsonSep 6, 2025
      If the generator has run for its maximum allowable time and the Auto Gen Start has stopped the generator and changed the AGS Mode to ManualOff, acknowledge the warning. Return the Auto Gen Start to the desired AGS Mode (Automatic or ManualOn). Ensure the generator is fueled and is supplying required power for battery charging and loads.
  • H
    hansenkimSep 8, 2025
    What to do if Xantrex Portable Generator max generator cycles reached?
    • J
      jessica08Sep 8, 2025
      If the generator has reached its maximum number of start-and-stop cycles and to help prevent an unattended generator from starting, the Auto Gen Start changed the AGS Mode to ManualOff, acknowledge the warning. Return the Auto Gen Start to the desired AGS Mode (Automatic or ManualOn). Ensure the generator is fueled and is supplying required power for battery charging and loads.

Summary

Important Safety Instructions

General Precautions

General safety guidelines and precautions for using the Auto Gen Start.

Hazard Warnings

Precautions related to explosive gases and FCC compliance.

Installation Guide

Preparing for Installation

Steps for planning and gathering tools/materials for installation.

Installation Steps

Procedures for mounting the unit and making external connections.

Troubleshooting Guide

Faults and Warnings Overview

Understanding and responding to fault and warning messages displayed by the Auto Gen Start.

Warning Messages

List and explanation of common warning messages and their causes/actions.

Fault Messages

List and explanation of fault messages, their causes, and required actions.