What to do if Xantrex Automatic Generator Portable Generator selected value failed to change?
- CClaudia GrimesSep 12, 2025
If you have tried to change the Gen Type without putting the system into Safe mode first, press “continue,” put the system into Safe mode, change the Gen Type, then return the system to Operating mode. Also, if you have tried to set the “Exercise Dur” for longer than “Max Run Time,” or “Max Run Time” for less than “Exercise Dur,” press “continue” and ensure that “Max Run Time” is set for longer than “Exercise Dur.”