EasyManua.ls Logo

Xantrex Trace DR Series - Page 34

Xantrex Trace DR Series
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
2.0 INSTALLATION
©2000 Xantrex Technology Inc.
Table 4
Minimum Recommended Wire Size (Input and Output)
Inverter Model
AC Input AC Output
120 VAC 220-240 VAC 120 VAC 220-240 VAC
DR1512
#8 or 6 AWG #10 AWG #12 AWG #16 AWG
DR2412
#6 AWG #10 AWG #10 AWG #14 AWG
DR1524
#8 or 6 AWG #10 AWG #12 AWG #16 AWG
DR2424
#8 AWG #10 AWG #10 AWG #14 AWG
DR3624
#6 AWG Not Available #8 AWG Not Available
975-0012-007
AC Wiring
Before wiring the input of the inverter, refer to the table below for the minimum recommended
wire size.
NOTE: Refer to the NEC for actual wire sizes for specific installations.