2.0 INSTALLATION
©2000 Xantrex Technology Inc.
Generators (continued)
Basic 120 VAC Utility/Generator Hookup
If a generator is used as a backup for the utility, then a manual transfer switch must be added
to provide a means to switch the generator power to the inverters inputs. The generator can be
used during extended outages to recharge the batteries and provide pass through power for the
loads. Start and stop the generator manually using the generators pull-cord, ON/OFF switch, etc.
Generator Connections (to manual bypass switch)
Connect a (green) ground wire between the generators GROUND terminal and the
GROUND terminal in the manual bypass switch.
Connect a (white) neutral wire between the generators NEUTRAL terminal and the
NEUTRAL bus in the manual bypass switch.
Connect a (black - HOT) wire between the generators HOT OUT terminal and the
GENERATOR (HOT) contact in the manual bypass switch.
NOTE: Refer to the bypass switch installation manual for contact details, torque specifications, etc.
Utility Connections (to manual bypass switch)
Connect a (green) wire between the GROUND terminal in the MAIN UTILITY PANEL and the
GROUND terminal in the manual bypass switch.
Connect a (white) wire between the NEUTRAL bus in the MAIN UTILITY PANEL and the
NEUTRAL bus in the manual bypass switch.
Connect a (black) wire between the inverter circuit breaker in the MAIN UTILITY PANEL and
the UTILITY HOT contact in the manual bypass switch.
Inverter Connections (to manual bypass switch)
Connect a (green) wire between the GROUND terminal in the manual bypass switch and the
inverters AC GROUND terminal.
Connect a (white) wire between the NEUTRAL terminal in the manual bypass switch and the
inverters NEUTRAL IN terminal.
Connect a (black) wire between the COMMON terminal in the manual bypass switch and the
inverters HOT IN terminal.
Torque all wires 16 in/lb.
Sub-panel Connections
Connect a (green) wire between the inverters AC GROUND terminal and the GROUND
terminal in the sub-panel.
Connect a (white) wire between the inverters NEUTRAL OUTPUT terminal and the
NEUTRAL bus in the sub-panel.
Connect a (black) wire between the inverters terminal labeled AC HOT OUTPUT and the
SUB-PANELs INPUT circuit breaker.
Torque all inverter terminal block connections to 16 inch-pounds. Refer to the sub-panel
manufacturers specifications for wire torques.
Recheck all connections.
Refer to the illustration on the next page.