reduction.
Excessive ambient
temperature
(1) Enhance ventilation measures
to reduce ambient temperature;
(2) Check whether the fan rotates
when the servo is enabled; when
the module temperature U-06
≥45℃, the fan opens.
Fan damage Replace the fan
1 E-061 Motor overheat
Alarm when motor
temperature is higher
than 95 ℃
(1) Check whether the motor
fan is abnormal;
(2) Contact the manufacturer
for technical support
3 E-063
Thermistor
disconnection alarm
(1) The thermistor of
11kw and above motor
is disconnected (2)
False opening detection
and disconnection alarm
of motors below 11kw
Check the connection of external
thermistor;
Shielding thermistor disconnection
alarm: P0-69.1 = 1
08 0 E-080 Overspeed (actual
speed ≥ P3-21/P3-22)
The maximum forward
speed is P3-21 and the
maximum reverse
speed is P3-22.
Motor code not match
Check if the driver P0-33 is
identical with the motor code of the
motor label (the number after
MOTOR CODE), if not, please
change to the same one, then power
on again.
UVW wiring error
Inspection of motor UVW wiring,
need to be connected in phase
sequence.
Motor speed too fast (1) The maximum speed limit value
P3-21/P3-22 was reduced.
(2) To confirm whether the external
force makes the motor rotate too
fast, whether the pulse input
frequency is too high, and whether
78