Parameter Description Range Unit Default
Ac
Acceleration Time -
Minimum time required
for the frequency of the
motor to go from
minimum to maximum
frequency.
01–20 Hz/sec 10
dc
Deceleration Time -
Minimum time required
for the frequency of the
motor to go from
maximum to minimum
frequency.
01–20 Hz/sec 10
Ld
Load Defaults - Select 1 to
set the all parameters to
default.
0 = no
1 = yes
NOTICE:
Editing the parameters can cause the controller to malfunction. Contact service at 844–
995–7867 for assistance.
(*) these values depend on the type of installation and are compatible with all the various
types of system.
5.4 ART function (Automatic Reset Test)
The A1 No Water and A4 Minimum Pressure alarms reset according to the Automatic
Reset Test (ART) function.
When either alarm is triggered with the Error LED (8) illuminated, the controller does an
automatic reset test. For the first instance of the alarm, the controller will restart the pump
after 5 minutes. If the alarm triggers again, the controller attempts to restart the pump
after 30 minutes. If the alarm continues, the controller attempts to restart the pump every
30 minutes over the next 24 hours.
If the alarm continues after these attempts, the controller stays locked out and requires a
manual alarm reset of the alarm to restart the pump. During the ART attempts, it is
possible to reset the alarm as indicated in Alarms and warnings on page 24.
To disable the ART function, it is necessary to disable the MINIMUM PRESSURE function
by setting NP (Minimum Pressure Setting) to 0.0.
5 System Description
ResiBoost INSTRUCTION MANUAL 23

Related product manuals