5.2 EMC requirements (Electromagnetic compatibility)
The EMC requirements in general differ between two environments which depending on
the intended use.
First environment – class B (EN 61800-3: Class C2)
Environment that includes domestic premises, it also includes establishments directly
connected without intermediate transformers to a low-voltage power supply network
which supplies buildings used for domestic purposes e.g. houses, apartments, commercial
premises or offices in a residential building are typical examples of first environment
locations.
Be careful: The relevant EMC regulations for which the HYDROVAR is tested in the first
environment consider that the HYDROVAR is a restricted available product. That means the
voltage of the inverter is less than 1000 V, it is neither a plug in device nor a movable
device and, when used in the first environment, is intended to be installed and
commissioned only by a person or an organisation having necessary skills in installing
and/or commissioning power drive systems, including their EMC aspects.
Second environment – class A (EN 61800-3: Class C3)
Environment that includes all establishments other than those directly connected to a low
voltage power supply network which supplies buildings used for domestic purposes e.g.
Industrial areas, technical areas of any building fed from a dedicated transformer are
typical examples of second environment locations.
The HYDROVAR complies with the general EMC regulations and is tested according
to the following standards: EN 61800-3/2004
EN 55011 (2002) Disturbance voltages / Disturbance field strength
First environment
– class B / class C2
Second Environment
– class A / class C3
Disturbance voltages OK OK
Disturbance field strength *) OK
*) Warning - In a domestic environment, this product may cause radio interference, in which case
supplementary mitigation measures may be required.
EN 61000-4-2 (2001) Electrostatic discharge
EN 61000-4-3 (2002) Electromagnetic field immunity test
EN 61000-4-4 (2001) Burst immunity test
EN 61000-4-5 (2001) Surge immunity test
EN 61000-4-6 (1996) Immunity of conducted RF-Disturbance

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem HYDROVAR HV 2.015 and is the answer not in the manual?

Xylem HYDROVAR HV 2.015 Specifications

General IconGeneral
BrandXylem
ModelHYDROVAR HV 2.015
CategoryController
LanguageEnglish

Related product manuals