Modbus RTU
Option module for PolluTherm
M H 6123 INT, page 1
1. Use of the option module
The Modbus RTU option module is used to connect the PolluTherm heat meters
to Modbus RTU network using EIA-485 channel.
Picture 1: Modbus RTU module
The module is based on Modbus RTU Slave protocol which is realized according to newest specifications
published by Modbus. The module EIA-485 network interface is compliant to TIA/EIA-485 standard.
1.1. Power supply
The Modbus RTU module should be powered by AC or DC (polarity insensitive) SELV power supply only.
SELV Power Supply Voltage 12-24 V AC/DC ±10%
Power Supply Terminals 60 and 61 (polarity insensitive)
Power Consumption max. 0.6 W
Typical Supply Current 32 mA @12 V DC
1.2. Communication interface
Connection to Modbus RTU network is realized by using galvanic isolated EIA-485 network interface.
Communication Protocol Modbus RTU
Network Polarity 90 (non-inverting, +) and 91 (inverting, -)
Transmission Speed/Baud Rate (bits per second) 1200, 2400, 4800, 9600, 14400, 19200,
38400, 56000, 57600, 115200
Data Format 8E1 (8 data bits, even parity bit, 1 stop bit),
8O1 (8 data bits, odd parity bit, 1 stop bit),
8N1 (8 data bits, none parity bit, 1 stop bit),
8N2 (8 data bits, none parity bit, 2 stop bits)
Galvanic Isolation between Network and Option Module 299 V
RMS
(0-60 Hz)
Number of Devices per EIA-485 Segment Channel Up to 256 ( UL)
EIA-485 Network Topology Bus Topology
EIA-485 Segment Channel Length 1200 m
The default communication parameters are: 9600 bps baud rate, 8N1 data format, Modbus Slave ID – 1.
Use only the dedicated two terminators on both ends of EIA-485 network channel segment. In case of any
question, please contact technical support.
1.3. Environmental requirements
Operating Temperature (ambient) +5 to +50°C
Storage Temperature -10 to +65°C
Operating and Storage Humidity 25 to 90 % RH @50°C, non-condensing
Question and Answer IconNeed help?

Do you have a question about the Xylem Sensus Modbus RTU and is the answer not in the manual?

Xylem Sensus Modbus RTU Specifications

General IconGeneral
BrandXylem
ModelSensus Modbus RTU
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals