29
Chapter 5. COMMUNICATION DATA TABLE
Item Data range
RAM EEPROM
Remarks
Address
RW
Address
RW
Decimal Decimal
(Hexadecimal) (Hexadecimal)
Station address 0: Communications 2030 5030
setting function disabled (07EE) (13A6)
1 to 127: Station address
Transmission 0: 38400bps 2031 5031
speed selection 1: 19200bps (07EF) (13A7)
2: 9600bps
3: 4800bps
4: 2400bps
Data format selection
0: 8 data bits, even parity, 2032 5032
1 stop bit (07F0) (13A8)
1: 8 data bits, no parity,
2 stop bits
SP limit function 0: SP limit function 2035
❍❍ 5035 ❍❍
disabled (07F3) (13AB)
1: Only upper limit enabled
2: Only lower limit enabled
3: Upper and lower limits
enabled
Operational 0: Low differential pressure 2036 ❍❍ 5036 ❍❍
differential pressure (50 ± 50kPa) (07F4) (13AC)
setting (control 1: Standard differential
optimization) pressure (200 ± 100kPa)
2: High differential pressure
(300+0, -100kPa)
Flow rate display 0: Flow rate is displayed in 2037
❍❍ 5037 ❍❍
unit change func- the standard flow rate (07F5) (13AD)
tion unit.
1: Flow rate is displayed in
[L/min] fixed.
-1:Flow rate is displayed in
[mL/min] fixed.
PV (instantaneous 0: Decimal point position is 2038
❍❍ 5038 ❍❍
flow rate) display not changed (07F6) (13AE)
decimal point posi- 1: Decimal point position is
tion change function shifted one digit left
-1:Decimal point position is
shifted one digit right
This func-
tion is valid
only for the
MQV9200/
95
00/0002/
0005.
This func-
tion is in-
valid for the
MQV0050
(J, K).
Though a
normal
termination
code is
returned
after
sending the
write
instruction
message,
the data
cannot be
written.