GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
30
Table 5-4 Drive Parameters (continued)
Parameter ADDR Name Set
Description
Default
0 Disabled
n139 018Bh
Energy-Saving
Control
1 Enabled (Must Be In V/F Control Mode)
0
n140 018Ch
Energy-Saving
Coefficient K2
0.0 - 999.9 or 1000 - 6550
6
n141 018Dh
Energy-Saving
Voltage Low
Limiter @60hz
0 - 120% 50
n142 018Eh
Energy-Saving
Voltage Low
Limiter @6 Hz
0 - 25% 12
n143 018Fh
Power Supply
Average Time
1 - 200 (1 = 24ms) 1
n144 0190h
Search Voltage
Limiter
1 - 100% 0
n145 0191h
Search Step
@ 100%
0.1 - 10.0% 0.5
n146 0192h
Search Step
@5%
0.1 - 10.0% 0.2
n147 0193h
Motor Rated
Voltage
150.0 - 255.0 Volts
300.0 - 510.0 Volts
200.0
400.0
n148 0194h Reserved
3
n149 0195h
Pulse Input
Scaling
9
100 - 3300 (1 - 33khz) 2550
0 1440 Hz / Max. Output Frequency
1 1f Output
6 6f Output
12 12f Output
24 24f Output
n150 0196h
Pulse Monitor
Output
Frequency
36 36f Output
0
0 Enabled (Coast To Stop)
1 Enabled (Ramp To Stop - N020)
2 Enabled (Ramp To Stop - N022)
3 Enabled (Operation Continues, Alarm)
n151 0197h
Modbus
Time Out
Detection
4 Disabled
0
00.1Hz/1
10.01Hz/1
2 100% / 3000
n152 0198h
Modbus
Frequency
Reference Unit
30.1%/1
0
n153
11
0199h
Modbus
Slave Address
0-31 0
0 2400 Bps
1 4800 Bps
2 9600 Bps
n154
11
019Ah
Modbus
Baud Rate
3 19200 Bps
2
0EvenParity
1OddParity
n155
11
019Bh
Modbus
Parity
2NoParity
2
10
n156
11
019Ch
Modbus
Send Delay
0 - 65ms 10
0 Enabled
n157
11
019Dh
Modbus
RTS Control
1 Disabled (Rs-422; 1 To 1 Communication)
0
n158 019Eh
Motor Code
Energy Saving
Control
0-70
6