No. Name Description
E2-04 Number of Motor Poles
Sets the number of motor poles.
Automatically set during Auto-Tuning.
E2-05
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance.
Automatically set during Auto-Tuning.
E2-06
Motor Leakage
Inductance
Sets the voltage drop due to motor leakage
inductance as a percentage of motor rated
voltage. Automatically set during
Auto-Tuning.
E2-11 Motor Rated Power
Sets the motor rated power in kilowatts (1
HP = 0.746 kW). Automatically set during
Auto-Tuning.
E2-20
Motor Service Factor
Amps
Sets the Motor Overload Current level for
oL1 fault.
F5-07
Terminal M1-M2
Output Selection
Sets the function for contact output
terminals M1-M2.
F5-08
Terminal M3-M4
Output Selection
Sets the function for contact output
terminals M3-M4.
F5-09
DO-A3 Output Mode
Selection
0: Output terminals are each assigned
separate output functions.
1: Binary code output.
2: Use output terminal functions selected by
parameters F5-01 through F5-08.
H1-01 to
H1-08
Multi-Function Digital
Input Terminals S1 to
S8 Function Selection
Assigns functions to the multi-function
digital inputs.
H2-01
Terminal M1-M2
function selection
(relay)
Sets the function for contact output
terminals M1-M2.
H2-02
Terminal M3-M4
function selection
(relay)
Sets the function for contact output
terminals M3-M4.
H2-03
Terminal MD-ME-MF
Function Selection
Sets the function for contact output
terminals MD-ME-MF.
H2-06
Watt Hour Output Unit
Selection
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
H3-01
Terminal A1 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input
terminal A1 for a current
or voltage input signal.
H3-02
Terminal A1 Function
Selection
Sets the function of terminal A1.
H3-03
Terminal A1 Gain
Setting
Sets the level of the input value selected in
H3-02 when 10 V is input at terminal A1.
H3-04
Terminal A1 Bias
Setting
Sets the level of the input value selected in
H3-02 when 0 V is input at terminal A1.
H3-05
Terminal A3 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input
terminal A3 for a current
or voltage input signal.
H3-06
Terminal A3 Function
Selection
Sets the function of terminal A3.
H3-07
Terminal A3 Gain
Setting
Sets the level of the input value selected in
H3-06 when 10 V is input at terminal A3.
H3-08
Terminal A3 Bias
Setting
Sets the level of the input value selected in
H3-06 when 0 V is input at terminal A3.
No. Name Description
H3-09
Terminal A2 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input
terminal A2 for a current
or voltage input signal.
H3-10
Terminal A2 Function
Selection
Sets the function of terminal A2.
H3-11
Terminal A2 Gain
Setting
Sets the level of the input value selected in
H3-10 when 10 V (20 mA) is input at
terminal A2.
H3-12
Terminal A2 Bias
Setting
Sets the level of the input value selected in
H3-10 when 0 V (0 or 4 mA) is input at
terminal A2.
H3-13
Analog Input Filter
Time Constant
Sets a primary delay filter time constant for
terminals A1, A2, and A3. Used for noise
filtering.
H3-14
Analog Input Terminal
Enable Selection
Determines which analog input terminals
will be enabled when a digital input
programmed for “Analog input enable”
(H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
H3-16 Terminal A1 Offset
Adds an offset when the analog signal to
terminal A1 is at 0 V.
H3-17 Terminal A2 Offset
Adds an offset when the analog signal to
terminal A2 is at 0 V.
H3-18 Terminal A3 Offset
Adds an offset when the analog signal to
terminal A3 is at 0 V.
H4-01
Multi-Function Analog
Output Terminal FM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal FM.
Set the desired monitor parameter to the
digits available in Uo-oo.
For example, enter “103” for U1-03.
H4-02
Multi-Function Analog
Output Terminal FM
Gain
Sets the signal level at terminal FM that is
equal to 100% of the selected monitor
value.
H4-03
Multi-Function Analog
Output Terminal FM
Bias
Sets the signal level at terminal FM that is
equal to 0% of the selected monitor value.
H4-04
Multi-Function Analog
Output Terminal AM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the
digits available in Uo-oo.
For example, enter “103” for U1-03.
H4-05
Multi-Function Analog
Output Terminal AM
Gain
Sets the signal level at terminal AM that is
equal to 100% of the selected monitor
value.
H4-06
Multi-Function Analog
Output Terminal AM
Bias
Sets the signal level at terminal AM that is
equal to 0% of the selected monitor value.
H4-07
Multi-Function Analog
Output Terminal FM
Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
H4-08
Multi-Function Analog
Output Terminal AM
Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
H5-01 Drive Node Address
Selects drive station node number (address)
for MEMOBUS/Modbus terminals R+, R-,
S+, S-. Cycle power for the setting to take
effect.