EasyManua.ls Logo

YASKAWA iQpump1000 - Main Circuit Terminal Functions

YASKAWA iQpump1000
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
u
Main Circuit Terminal Functions
Table i.2 Main Circuit Terminal Functions
Terminal Type
Function Page
200 V
Class
Drive Model
2A0004 to
2A0081
2A0110, 2A0138
2A0169 to
2A0415
400 V
Class
4A0002 to
4A0044
4A0058, 4A0072
4A0088 to
4A0675
4A0930, 4A1200
600 V
Class
5A0003 to
5A0032
5A0041, 5A0052
5A0062 to
5A0242
R/L1
Main circuit power supply input
Connects line power to the
drive
20
S/L2
T/L3
R1-L11
Not available
Main circuit power
supply input
Connects line power to the
drive
Remove the shorting bars
connecting R/L1-R1/L11,
S/L2-S1/L21, T/L3-T1/L31
when using 12-phase
rectification.
S1-L21
T1-L31
U/T1
Drive output Connects to the motor 20V/T2
W/T3
B1
Braking resistor Not available
Available for connecting a
braking resistor or a braking
resistor unit option
B2
2 DC link choke
connection
(1, 2)
(remove the
shorting bar
between
1 and 2)
DC power
supply input
(1, )
Not available
For connecting:
the drive to a DC power
supply
dynamic braking options
a DC link choke
1
DC power supply
input
(1, )
DC power supply input (1, )
Braking unit connection (3, )
3
Not available
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less
For 600 V class: 10 Ω or less
Grounding terminal 35
Note: Use terminals B1 and when installing a CDBR-type braking unit on drives with built-in braking transistors (Models 2A0004 to 2A0138,
4A0002 to 4A0072, and 5A0003 to 5A0052).
Wiring Fuses for Models 4A0930 and 4A1200
NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage
current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from Table i.3.
Table i.3 Input Fuses for Models 4A0930 and 4A1200
Voltage
Class
Model
Selection Input Fuse (Example)
Input Voltage Current
Pre-arc
I
2
t (A
2
s)
Model Manufacturer Rating
Pre-arc
I
2
t (A
2
s)
Three-
Phase
400 V
Class
4A0930 480 V 1500 A
140000 to
3100000
CS5F-1200 Fuji Electric AC500 V, 1200 A 276000
FWH-1200A Bussman AC500 V, 1200 A
4A1200 480 V 1500 A
320000 to
3100000
CS5F-1500 Fuji Electric AC500 V, 1500 A 351000
FWH-1600A Bussman AC500 V, 1600 A
i.4 Electrical Installation
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
25

Table of Contents

Other manuals for YASKAWA iQpump1000