J
Jackie PadillaSep 8, 2025
Why is my YASKAWA Controller showing l Fault?
- AandrewskyleSep 8, 2025
The torque limit was reached during deceleration for longer than 3 sec. when in Open Loop Vector control because the load inertia is too big, the torque limit is too low, or the motor parameters are wrong. Check the load, set the torque limit to the most appropriate setting (L7-01 through L7-04), and check the motor parameters.
 