8 Standards Compliance
YASKAWA ELECTRIC TOBP C730600 95A U1000-Series Option PS-U10 Installation Manual 47
UL Standards
Figure 34
Figure 38 UL/cUL Mark
The UL/cUL mark applies to products in the United States and Canada and it means that UL
has performed product testing and evaluation and determined that their stringent standards
for product safety have been met. For a product to receive UL certification, all components
inside that product must also receive UL certification.
UL Standards Compliance
This product is evaluated in accordance with UL standard UL508C and complies with UL
requirements.
Installation Area
Do not install the product in a pollution degree 3 or 4 area (UL standard).
Ambient Temperature
IP00 enclosure: -10°C to +50°C
IP20/UL Type 1 enclosure: -10°C to +40°C
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national, state, or
local codes for wiring. The external power supply shall be a UL Listed Class 2 power supply
source or equivalent only.
Input: External power supply
Terminal Signal: 24, 0, FE
Power Supply Specifications: Requires class 2 power supply.