YASKAWA Z1000 - Page 17

YASKAWA Z1000
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
+
-
+
+
+
SN
AMFM
V
I
<1>
M
U/T1
V/T2
W/T
U
V
W
3
Ground
Cooling fan
M
+
-
+
+
+
S1
S2
S3
S4
S5
S6
S7
FE
A1
A2
0 V
AC
R
R
S
S-
IG
Drive
2 k
FM
AM
0 V
FM
AM
AC
FE
<9>
<9>
<7>
<7>
<8>
<6>
<3>
<2>
+V
MA
M1
M2
MB
MC
CN5
Forward Run / Stop
Reverse Run / Stop
External fault
Fault reset
Multi-speed step 1
Multi-speed step 2
Jog speed
Multi-function
digital inputs
(default setting)
Option card
connector
Shield ground terminal
Multi-function
analog inputs
Power supply +10.5 Vdc, max. 20 mA
Analog Input 1
(Frequency Reference Bias)
0 to +10 Vdc (20 k
W
)
4 to 20 mA / 0 to 20 mA (250 )
Analog Input 2
(Frequency Reference Bias)
0 to +10 Vdc (20 k
W
)
4 to 20 mA / 0 to 20 mA (250 )
+P
Termination resistor
(120 , 1/2 W)
DIP
Switch S2
Fault relay output
250 Vac, max. 2 A
30 Vdc, max 2 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (During Run)
250 Vac, max. 2 A
30 Vdc, max 2 A
(min. 5 Vdc, 10 mA)
Multi-function analog output 1
(Output frequency)
0 to +10 Vdc (2 mA)
4 to 20 mA
Multi-function analog output 2
(Output current)
0 to +10 Vdc (2 mA)
4 to 20 mA
Main Circuit
Control Circuit
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
r1
s1
t1
FU
FV
FW
R/L1
S/L2
T/L
+M
-M
3
Three-phase
power supply
200 V/400 V
50/60 Hz
Wiring sequence should shut off
power to the drive when a fault
output is triggered.
<10>
M 3
M 4
Multi-function relay output (Zero Speed)
250 Vac, max. 2 A
30 Vdc, max 2 A
(min. 5 Vdc, 10 mA)
M 5
M 6
Multi-function relay output (Speed Agree 1)
250 Vac, max. 2 A
30 Vdc, max 2 A
(min. 5 Vdc, 10 mA)
A2A1
V
I
Jumper S1
A1/A2 Volt./Curr.
Selection
R
S
T
Main
Switch
Fuse
12-Pulse/18-Pulse
Rectification
Jumper S5
AM/FM Volt./Curr.
Selection
SC
<4>
+24 V
Sink / Source mode
selection wire link
(default: Sink)
SP
<5>
ON
SW1
OFF
ON
SW2
OFF
APOGEE FLN Comm.
RS-422/RS-485
48 kbps
BACnet Comm.
RS-485
max. 76.8 kbps
MEMOBUS/Modbus
comm. RS-422/RS-485
max. 115.2 kbps
Metasys N2 Comm.
RS-422/RS-485
96 kbps
3 k (8 mA)
each input
Figure i.10 Drive Standard Connection Diagram (example: 2A0011)
<1> Self-cooling motors do not require the same wiring necessary for motors with cooling fans.
i.4 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
17