No. Item Page
17
Set up overload protection circuits when running multiple motors from a single drive.
M1
OL1
OL2
OLn
MC1
MC2
MCn
M2
Mn
Drive
MC1 - MCn
OL 1 - OLn
... magnetic contactor
... thermal relay
Power supply
Note: Close MC1 – MCn before operating the drive. MC1 – MCn cannot be switched off during run.
18 Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the drive.
Control Circuit Wiring
19 Use twisted-pair line for all drive control circuit wiring. 31
20 Ground the shields of shielded wiring to the GND terminal. 31
21 For 3-Wire sequence, set parameters for multi-function contact input terminals S1 to S7, and wire control circuits.
22 Properly wire the option card. 31
23 Check for any other wiring mistakes. Only use a multimeter to check wiring.
24 Properly fasten drive control circuit terminal screws. 23
25 Pick up all wire clippings.
26 Ensure that no frayed wires on the terminal block are touching other terminals or connections.
27 Properly separate control circuit wiring and main circuit wiring.
28 Analog signal line wiring should not exceed 50 m.
i.4 Electrical Installation
40
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide