Installation Method for 2A0343, 2A0396, and 4A0361 to 4A0590
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive
also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
A
B
D
E
C
M
U/T1
V/T2
W/T3
U
V
W
A Drive
B 10 m max. cable length between
drive and motor
C Motor
D Metal conduit
E Ground wire should be as short as
possible.
Figure i.60 Installation Method
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4
o
0240 and larger, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor or a protective earthing conductor with a cross-section of at least 10 mm
2
(Cu) or 16 mm
2
(Al) must be used. Failure to
comply may result in death or serious injury.
C
B
A
A Braided shield cable
B Metal panel
C Cable clamp (conductive)
Figure i.61 Ground Area
i.9 Standards Compliance
80
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide