Three-Phase 200 V / 400 V Class (2A0343, 2A0396, and 4A0361 to 4A0590)
R/L1 S/L2 T/L3
U/T1
V/T2
W/T3
3
+
1
+
2A0343 and 2A0396
4A0414 to 4A0590
L3
L2
L1
L3L3 L2L2 L1L1L3 L2 L1
E
PE
B
C
D
E
D
F
H
G
A
K
I
J
A Ground the cable shield
B Enclosure panel
C Metal plate
D Grounding surface (remove any
paint or sealant)
E Drive
F Motor cable (braided shield cable,
max. 10 m)
G Motor
H Cable Clamp
I Ground plate (scrape off any
visible paint)
J EMC noise filter
K Make sure the ground wire is
grounded
Figure i.63 EMC Filter and Drive Installation for CE Compliance (2A0343, 2A0396, and 4A0361 to 4A0590)
n
EMC Filters
Install the drive with the EMC filters listed in Table i.33 for 2A0343, 2A0396, and 4A0361 to 4A0590.
Table i.33 IEC/EN 61800-3 Filters
Model
Filter Data (Manufacturer: Schaffner)
Type Rated Current (A) Weight (lb)
Dimensions
[W x D x H] (in)
Y x X (in)
Three-Phase 200 V Class
2A0343
2A0396
FS5972-600-99 600 24.3 10.2 × 5.3 × 15.2 9.3 × 4.7
Three-Phase 400 V Class
4A0361 FS5972-410-99 410 23.1 10.2 × 4.5 × 15.2 9.3 × 4.7