EasyManua.ls Logo

YOKOGAWA AXF series - Page 87

YOKOGAWA AXF series
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 01E20D01-01E
6-29
6. OUTLINE
Table of Optional Specifications (continued)
T26-4.EPS
Code
Remote
Flowtube
Integral
Flowmeter
Remote
Flowtube
Remote
Flowtube
Integral
Flowmeter
Remote
Flowtube
Integral
Flowmeter
Submersible
Sanitary
Applicable Model
General
Item
Specifications
A flow test near 0, 25, 50, 75, and 100% of the user-specified span is
performed instead of the flow test of the standard 2m/s span and a test
certificate (QIC) is submitted. Specify the span (100% flow span) whose
corresponding flow velocity lies between 0.5 to 10 m/s (0.8 to 10 m/s for
sizes 32, 65, and 125 mm) and that is less than the maximum line capacity.
Selectable range of flow rate span is showing below.
Selectable range of flow rate span : m
3
/h
(Flow rate span velocity : m/s)
0.009 (0.5) to 0.05 (2.83)
0.036 (0.5) to 0.2 (2.83)
0.15 (0.5) to 0.96 (3.40)
0.32 (0.5) to 2.8 (4.40)
0.89 (0.5) to 11 (6.22)
2.32 (0.8) to 28.9 (10.00)
2.27 (0.5) to 28.0 (6.30)
3.54 (0.5) to 56 (7.92)
9.56 (0.8) to 80 (6.70)
9.05 (0.5) to 126 (6.96)
14.2 (0.5) to 190 (6.72)
35.3 (0.8) to 300 (6.79)
31.9 (0.5) to 380 (5.97)
56.6 (0.5) to 670 (5.92)
88.4 (0.5) to 1000 (5.66)
128 (0.5) to 1200 (4.72)
174 (0.5) to 1200 (3.47)
227 (0.5) to 1350 (2.98)
Size : mm
(in.)
2.5 (0.1)
5 (0.2)
10 (0.4)
15 (0.5)
25 (1)
32 (1.25)
40 (1.5)
50 (2)
65 (2.5)
80 (3)
100 (4)
125 (5)
150 (6)
200 (8)
250 (10)
300 (12)
350 (14)
400 (16)
Explosion proof
FM Explosion proof
See “HAZARDOUS AREA CLASSIFICATION”
ATEX Certification
ATEX Explosion proof
See “HAZARDOUS AREA CLASSIFICATION”
CSA Certification
–– –––CF1
IECEx
Certification
IECEx Explosion proof
See “HAZARDOUS AREA CLASSIFICATION”
–– –––SF2
TIIS Certification
TIIS Flameproof
See “HAZARDOUS AREA CLASSIFICATION”
––
–––JF3
(*8)
–– –––KF2
CSA Explosion proof, Dual Seal
See “HAZARDOUS AREA CLASSIFICATION”
AXF***G-
D
E
F
G
AXF***G-
N
P
AXF***C-
D
E
F
G
AXF***C-
N
P
AXF***W-
N
P
AXF***H-
D
E
F
G
AXF***H-
N
P
Enhanced Dual
Frequency Excitation
(*6)
Available for 25 to 200 mm (1.0 to 8.0 in.) sizes.
Products are delivered with the Standard dual frequency excitation mode
and the Enhanced dual frequency excitation mode enabled.
Although the meter factors for the Standard dual frequency excitation mode
and the Enhanced dual frequency excitation mode are inscribed on the
name plate, the flow calibration of optional code HF1 is not performed in
Enhanced dual frequency excitation.Excitation mode select optional code
HF2 when an accurate flow measurement is required.
Available for 25 to 200 mm (1.0 to 8.0 in.) sizes.
Products are delivered with the Standard dual frequency excitation mode
and the Enhanced dual frequency excitation mode enabled.
The meter factor for the Enhanced dual frequency excitation obtained by
flow calibration is inscribed on the name plate and set into the combined
converter in addition to the meter factor for the Standard dual frequency
excitation.
HF1
HF2
 SC
–– –––FF1
Five-point Calibration
in User-specified
Span
FM Approval
Flameproof packing
adapter for TIIS
Flameproof Type (*7)
Two flameproof packing adapters
–– –––G12
One flameproof packing adapter and a blanking plug.
Available for integral flowmeter and only when a four-wire cable is used for
power input and signal output with a 24V power supply.
––
–––G11
(*9)
: Available –: Not available

Table of Contents

Related product manuals