1. System Installation Requirements
1-17
TI 32P01J10-01EN
Cabling
Observe the following when cabling the power unit to the ProSafe-RS system equipment:
Protect signal cables from induced noise.
Protect signal cables from induction from high-voltage power lines.
Separate the ProSafe-RS system power supply from other equipment power supplies.
Use a separate power distribution board.
Provide a dedicated breaker for each power supply.
Install breakers and devices in the same room.
Label the breakers with the name of the connected equipment.
Install the breakers where they can be easily operated.
The breaker, must not interrupt connection by wiring to protective grounding system.
As far as possible install power supply cables and high-voltage power lines in metallic
conduits.
Use shielded cables if metallic conduits cannot be provided.