1. System Installation Requirements
1-35
TI 32P01J10-01EN
F010801.ai
AC/DC
DC/DC
AC/DC
DC/DC
Safety Control Unit
Tap
Noise Filter
(*2)
Noise Filter
(*1)
Tap
Tap
Power feed
Safety Node Unit
External PSU
Cabinet
AC/DC
DC/DC
Safety Node Unit
Tap Tap
Tap
Power feed
External PSU
Cabinet
Safety Control Unita
AC/DC
DC/DC
Noise Filter
(*2)
Noise Filter
(*1)
Safety Control Unit
Noise Filter
(*2)
Noise Filter
(*2)
Tap
Power feed
Safety Node Unit
External PSU
Cabinet
AC/DC
DC/DC
AC/DC
DC/DC
Cabinet
Safety Control Unit
Noise Filter
(*3)
Tap
Power feed
Safety Node Unit
External PSU
AC/DC
DC/DC
AC/DC
DC/DC
(a) (b)
(c) (d)
Noise Filter
(*1)
Figure Wiring for power cables
*1: This noise lter is for the power line of SPW48, S2PW50, and FAN. Refer to "Table Example of a noise lter for the power line
of SPW48, S2PW50, and FAN.".
*2: This noise lter is for the external power supply unit. Regarding necessity of the noise lter, please follow directions on
instructions for marine standards of this external power supply unit.
*3: If the noise lter for the external power supply unit is equivalent to the ones of "Table Example of a noise lter for the power line of
SPW48, S2PW50, and FAN.", both noise lters can be shared.
The following table shows example of a noise lter.
Table Example of a noise lter for the power line of SPW48, S2PW50, and FAN.
Category Manufacturer Model no. Power Source
Noise lter
OKAYA Electric Industries
Co., LTD
SUP-P30H-EPR-4 100 - 120 V AC, 220 - 240 V AC (*1)
SUPH-EX10-ER-6 100 - 120 V AC, 220 - 240 V AC
COSEL Co., LTD NBH-20-432 24 V DC (*2)
*1: For S2PW50, SUPH-EX10-ER-6 can be used.
*2: For expansion or modication of unit, the existing TDK Lambda PSHN-2020 can also be used.
IMPORTANT
Lay the incoming wires to a noise lter separately from its outgoing wires.
Minimize the wiring to the ground terminals of the noise lters to minimize the impedance.
Mar. 29, 2019-00