2. Transportation, Storage and Installation
2-8
TI 32P01J10-01EN
“Free-access” Floor
Clamp the equipment to pedestals that are anchored to the base oor.
Equipment
Free-access floor
Base floor
Pedestal
F020503.ai
Figure Using Pedestal
In the “free-access” oor, make holes for riser cables to connect to each piece of equipment as
follows:
If one oor tile is removed, be sure to reinforce the opening with an angle frame for oor
stability.
Free-access floor supports
Angle frame
F020504.ai
Figure Removing One Floor Tile
Do not make a holes near the oor supports.
Do not cut away more than 1/3 of a oor tile.