Mounting the Instrument Main Unit
Provideaninstrumentedpanelsteelsheetof1to10mmthickness.
Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstall
the controller:
1) Insert the controller into the opening from the frontof the panelso thatthe
terminalboardontherearisatthefarside.
2) Setthebracketsinplaceonthetopandbottomofthecontrollerasshowninthe
gurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertighten
them.
CAUTION
Tighten the screws with appropriate tightening torque within 0.25
N•m. Otherwise it may cause the case deformation or the bracket
damage.
Make sure that foreign materials do not enter the inside of the
instrument through the case’s slit holes.
n
External Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]
117 (4.61) min.
145 (5.71)
min.
+0.8
0
+0.8
0
92
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11
(0.43)
UP55A
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
Bracket
Bracket
94.6 (3.72)
91.6 (3.61)
105.2 (4.14)
Unit: mm (approx. inch)
96 (3.78)
96 (3.78)
• General mounting • Side-by-side close mounting
Terminal cover
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8
0
92
+0.03
0
(3.62 )
(0.98)
+0.03
0
(3.62 )
+0.8
0
92
+0.03
0
(3.62 )
([(N-1)×3.78+3.62] )
+0.03
0
4. HardwareSpecications
WARNING
This instrument is for Measurement Category I (CAT.I). Do not use it
for measurements in locations falling under Measurement Catego-
ries II, III, and IV.
Internal Wiring
Outlet
Entrance IV
Cable
III
T
I
II
Category
Measurement
category
Description Remarks
I CAT.I
For measurements
performed on circuits not
directlyconnectedtoMAINS.
-
II CAT.II
For measurements
performed on circuits di-
rectlyconnected
tothelow-voltageinstallation.
Appliances,portableequip-
ments, etc.
III CAT.III
Formeasurements
performedinthebuilding
installation.
Distributionboard,
circuit
breaker,etc.
IV CAT.IV
For measurements
performed at the source of
thelow-voltageinstallation.
Overheadwire,cable
systems, etc.
n
InputSpecications
●UniversalInput(Equippedasstandard)
• Numberofinputs:1
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type
Instrument Range
Accuracy
ºC ºF
Thermo-
couple
K
-270.0to
1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%of
instrumentrange±1digitfor
lessthan0°C
±2%of
instrumentrange±1digitfor
lessthan-200.0°CofthermocoupleK
±1%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF
-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to
1200.0ºC -300.0to2300.0ºF
T
-270.0to
400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to
1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digit
for400°Cormore
±5%of
instrumentrange±1digitfor
lessthan400°C
S 0.0to
1700.0ºC 32to3100ºF
±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to
1300.0ºC -300.0to2400.0ºF
±0.1%ofinstrumentrange±1digit
±0.25%ofinstrumentrange±1digit
forlessthan0°C
E -270.0to
1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%of
instrumentrange±1digitfor
lessthan0°C
±1.5%of
instrumentrange±1digitfor
lessthan-200.0°CofthermocoupleE.
L -200.0to
900.0ºC -300.0to1600.0ºF
U
-200.0to
400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to
2300.0ºC 32to4200ºF
±0.2%ofinstrumentrange±1digit
(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to
1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor
800°Cormore
Accuracyis
notguaranteedforless
than800°C.
W97Re3-
W75Re25
0.0to
2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100
-200.0to500.0ºC -300.0to1000.0ºF
±0.1%ofinstrumentrange±1digit
(Note1)
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100
-200.0to
850.0ºC -300.0to1560.0ºF
±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0ºC -300.0to1000.0ºF
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal
0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V
4.00to20.00mA
DCvoltage/current
0.000to2.000V
0.00to10.00V
0.00to20.00mA
-10.00to20.00mV
0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpower
frequencyat50/60Hz.
Note
1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange
between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:Selectfrom100and200ms
• Burnout detection:
FunctionsatTC,RTD,andstandardsignal.
Upscale,downscale,andoffcanbespecied.
Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4
mAor
less.
•Inputbiascurrent:0.05µA(forTCorRTD)
•Measuredcurrent(RTD):About0.16mA
• Input resistance:
TCormVinput:1MΩormore
Vinput:About1MΩ
mAinput:About250Ω
•Allowablesignalsourceresistance:
TCormVinput:250Ωorless
Effectsofsignalsourceresistance:0.1µV/Ωorless
DCvoltageinput:2kΩorless
Effectsofsignalsourceresistance:About0.01%/100Ω
• Allowablewiringresistance:
RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires
shall
beequal.)
Wiringresistanceeffect:±0.1ºC/10Ω
• Allowableinputvoltage/current:
TC,mV,mAandRTDinput:±10VDC
Vinput:±20VDC
mAinput:±40mA
• Noiserejectionratio:
Normalmode:40dBormore(at50/60Hz)
Commonmode:120dBormore(at50/60Hz)
For100-240VAC,thepowerfrequencycanbesetmanually.
Automaticdetectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.
• Referencejunctioncompensationerror:
±1.0ºC(15to35ºC)
±1.5ºC(-10to15ºCand35to50ºC)
• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
●AuxiliaryAnalogInput
• Use:Remotesetpointsetting,externalcompensatinginput,auxiliaryinputforcom-
putation, etc.
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type Instrument Range Accuracy
Standardsignal
0.400to2.000V ±0.2%ofinstrumentrange±1digit
1.000to5.000V ±0.1%ofinstrumentrange±1digit
DCvoltage
0.000to2.000V ±0.2%ofinstrumentrange±1digit
0.00to10.00V ±0.1%ofinstrumentrange±1digit
DCvoltage
forhigh-input
impedance
0.000to
1.250V ±0.1%ofinstrumentrange±1digit
• Inputsampling(control)period:Sameasuniversalinput
• Inputresistance:About1MΩ
However,10MΩormoreforDCvoltageforhigh-inputimpedancerange
•Burnoutdetection:Functionsatstandardsignal
Burnoutisdeterminedtohaveoccurredifitis0.1Vorless.
●UniversalInput(Optionalsufxcode:/U1)
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype,instrumentrange,andmeasurementaccuracy:Sameasthestandard-
equippeduniversalinputexceptthetablebelow.
Input Type
Instrument Range
Accuracy
°C °F
4-wireR
TD
JPt100
-200.0to
500.0°C -300.0to1000.0°F
±0.5°Cofinstrumentrange±1digit
-150.00to150.00°C -200.0to300.0°F
±0.2°Cofinstrumentrange±1digit
Pt100
-200.0to850.0°C -300.0to1560.0°F
±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0°C -300.0to1000.0°F
±0.5°Cofinstrumentrange±1digit
-150.00to150.00°C -200.0to300.0°F
±0.2°Cofinstrumentrange±1digit
Note1
:±0.5°C±1digitintherangebetween-200.0and500.0°C/-300.0and1000.0°F.
• Inputsampling(control)period:Sameasthestandard-equippeduniversalinput.
• Burnoutdetection:Sameasthestandard-equippeduniversalinput.
n
AnalogOutputSpecications
• Numberofoutputs:
Controloutput:1
Cooling-sidecontroloutputofHeating/coolingtype:1
• Outputtype:Currentoutputorvoltagepulseoutput
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatin thestandardoperatingconditions: 23±2°C,55±10%RH,
and
powerfrequencyat50/60Hz.
• Voltagepulseoutput:
Use:Timeproportionaloutput
On-voltage:12Vormore/loadresistanceof600Ωormore
Off-voltage:0.1VDCorless
Timeresolution:10msor0.1%ofoutput,whicheverislarger
n
StepResponseTimeSpecications
Within500ms(whenthecontrolperiodis100ms)
Within1s(whenthecontrolperiodis200ms)
(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspan
isapplied)
n
TriacOutputSpecications
•Contacttypeandnumberofoutput:zerocross;1point
Loadvoltage:75to250VAC
Allowableloadcurrent:0.8Awhentheambienttemperatureis20°C,0.3Awhenthe
ambienttemperatureis50°C.
•Minimumloadcurrent:20mA(*)
*:Unusableforasmallloadof10mAorless.
*: If there is a riskofsurgecurrent, connectacurrent-limiting reactor, a current-
limitingfuseorabreakerinseriestotheloadpowersupply.
•Use:Timeproportionaloutput,Alarmoutput
•Time resolution ofcontroloutput:1/commercialfrequency (s)or0.1%ofoutput,
whicheverislarger.
n
RelayContactOutputSpecications
• Contacttypeandnumberofoutputs:
Controloutput:contactpoint1c;1point
Cooling-sidecontroloutputofHeating/coolingtype:contactpoint1c;1point
Eventoutput:contactpoint1a;3points(commonisindependent)
• Contactrating:
Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload)
Contactpoint1a(eventoutput):240VAC,1Aor30VDC,1A(resistanceload)
• Use:Timeproportionaloutput,eventoutput,alarmoutput,FAILoutput,etc.
• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislarger
Note:Thiscannotbeusedforasmallloadof10mAorless.
n
PositionProportionalOutputSpecications
• Positionsignalinput:
Slideresistance:100Ωto2.5kΩoftotalresistance
100%sideandslideline:withdisconnectiondetection
0%side:withoutdisconnectiondetection
Currentinput:4to20mA(withdisconnectiondetection)
• Samplingperiod:50ms
• Measurementresolution:0.1%ofinputspan
Position proportional relay output:
Contactpoint1a;2points,250VAC,3Aor30VDC,3A(resistanceload)
Note:Thiscannotbeusedforasmallloadof10mAorless.
n
RetransmissionOutputSpecications
• Number ofoutputs: Retransmissionoutput;1,sharedwith 15VDC looppower
supply
• Current
output:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
n
15VDCLoopPowerSupplySpecications
(Sharedwithretransmissionoutput)
• Powersupply:14.5to18.0VDC
• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
n
ContactInputSpecications
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype:No-voltagecontactinputortransistorcontactinput
• Inputcontactrating:12VDC,10mAormore
Useacontactwithaminimumon-currentof1mAormore.
• ON/OFFdetection:
No-voltagecontactinput:
Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact
resistanceof50kΩormoreas“OFF.”
Transistor contact input:
Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust
notexceed100µAwhen“OFF.”
• Minimumstatusdetectionholdtime:Controlperiod+50ms
• Use:PTNO.switch,operationmodeswitch,andeventinput
n
TransistorContactOutputSpecications
• Numberofoutputs:SeethetableofModelandSufxCodes.
• Outputtype:Opencollector(SINKcurrent)
• Outputcontactrating:Max.24VDC,50mA
• Outputtimeresolution:Min.100ms
n
HeaterBreakAlarmSpecications
• Numberofinputs:2
• Numberofoutputs:2(transistorcontactoutput)
• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)and
generatesaheater breakalarmwhenthemeasured valueislessthanthe break
detectionvalue.
• Currenttransformerinputresistance:About9.4Ω
• Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeap
-
plied.)
• Heatercurrentsettingrange:OFF,0.1to300.0Arms
Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms
Note:TheCTratiocanbeset.CTratiosettingrange:1to3300
• RecommendedCT:CTfromU.R.D.,Ltd.
CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms
CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms
• Heatercurrentmeasurementperiod:200ms
• Heatercurrentmeasurementaccuracy: ±5% of current transformer input range
span±1digit(CTerrorisnotincluded.)
• Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan
• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)