EasyManuals Logo

YOKOGAWA UP55A Operation Guide

YOKOGAWA UP55A
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
IM 05P02C41-15EN page 11/14
Operation Parameters / Program Parameters
HolddownthePARAMETERkeyfor3secondstomovefromtheOperationDisplayto
theOperationParameterSettingDisplay.PresstheDISPLAYkeyoncetoreturntothe
OperationDisplay.
Menu
DISPLAY
key
key key
key
key
The parameter groups can be switched using , keys.
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
Parameter
END
PROG
PTNO.
SEGNO.
END
Menu END
END
M e n u D i s p la y
and Pa ramet er
Setting Display
are changed in a
circular pattern.
Hold down PARAMETER key for 3 sec.
SET/ENTER key
1 to 30
SET/ENTER key
SET/ENTER
key
PARAMETER
key
PARAMETER
key
PARAMETER
key
0, 1 to 99
Parameter
Parameter
END
Move to the Setup Parameter Setting Display:
Hold down the PARAMETER key and the Left arrow key simultaneously for 3 sec.
Operation for Setting
· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrow
keytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset
-
pointblinking.
Theblinkingstateallowsyoutomakechanges(settingmode).Usethe
Up/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeyto
registerthesetting.
Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodel
andsufxcodes,controlmode(CTLM),controltype(CNT),etc.
The parameters for pro-
fessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
n
Operation Mode
Menusymbol:
(MODE)
Parameter
symbol
Name of Parameter Setting Range
Initial
value
User
setting
Display
level
(HOLD)
Pause/cancelreleaseof
programoperation
Displayduringprogramoperation.
ON:Pause
OFF:Cancelrelease(Programopera-
tionrestart)
OFF
EASY
(ADV)
Advanceofsegment
Displayduringprogramoperation.
Setas“ADV=ON”toadvancefrom
thecurrentsegmenttothenextseg-
ment.
OFF
(MODE)
Operationmode
RESET:Stopofprogramoperation
PROG:Startofprogramoperation
LOCAL:Startoflocal-modeoperation
REM:Startofremote-modeoperation
RESET
(A.M)
AUTO/MANswitch
AUTO:Automaticmode
MAN:Manualmode
MAN
(PTNO.)
Programpatternnumber
selection
0:Not
selectprogrampattern
1to30
0
(SST)
Start-of-programseg-
mentnumber
1to99
Thesettingvaluereturnsto“1”when
theprogramoperation(PROG)
changesintoRESET,LOCAL,or
REM.
1
(P.FWD)
Fast-forwardingof
programoperation
1:Normal,2:Twice,5:Fivetimes,
10:Ten
times
*Usethisfunctionwhenchecking
theprogrampatternsetting.Only
SegmenttimeandTimeeventcan
befaster.
*Theoperationreturnstothenormal
speedafterfast-forwarding.
1
(AT)
AUTO-tuningswitch
OFF:Disable
1to8:Performauto-tuning.Tuning
resultisstoredinthespecied
numberedPID.
R:TuningresultisstoredinthePID
forreferencedeviation.
OFF
(PID)
PIDnumber
ThePIDgroupnumberbeingselected
is displayed.
1to8,R:PIDgroupforreferencedeviation
1
n
SELECT Parameter
Menusymbol: (CS)
Parameter
symbol
Name of Parameter Setting Range
Initial
value
User
setting
Display
level
Registeredpa-
rametersymbol
SELECTparameter
10to19
Settingrangeofaregisteredparameter.
Fordetails,seeUser'sManual.
Table
below
EASY
Parameter n=10 n=11 n=12 n=13 n=14 n=15 n=16 n=17 n=18 n=19
CSn
Forthe
registrationofSELECTparameters,seeUser'sManual.
n
Program Setting Parameter
Menusymbol:( PROG> PTNO.(=01to30)> SEGNO.(=00))
Parameter symbol
Name of
Parameter
Setting Range
Initial
value
User
setting
Display
level
(SSP)
Startingtarget
setpoint
0.0to
100.0%ofPVinputrange(EU)
(Settingrange:P.RLtoP.RH)
P.RL
EASY
(STC)
Start code
SSP:Programoperationbeginswith
thestartingtargetsetpoint.
RAMP:Ramp-prioritizedPVstart
TIME:Time-prioritizedPVstart
LSP:Local-modestart
RSP:Remote-modestart
*STC=TIMEcannotbeselectedwhen
theparameterSEG.TisTM.RT.
SSP
to
(WT.SW1toWT.SW5)
Waitfunction
ON/OFF1to5
OFF:Disable
ON:Enable
OFF
STD
to
(WZ.UP1toWZ.UP5)
Upper-sidewait
zone1to5
0.0to10.0%ofPVinputrange(EU)
0.5%
ofPV
input
range
to
(WZ.LO1toWZ.LO5)
Lower-sidewait
zone1to5
0.5%
ofPV
input
range
to
(WT.TM1toWT.TM5)
Waittime1to5
OFF:Nofunction
0.00to999.59(“hour.minute”or“minute.second”)
*Availableonlyforthewaittimeatthesegment
switching.
*Use
theparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
OFF
(R.CYCL)
Numberof
repeat cycles
0to999,CONT(limitlessnumberof
times)
0
(R.STRT)
Repeatcycle
startsegment
number
1to
99
1≤R.STRT≤R.END≤99
1
(R.END)
Repeatcycle
endsegment
number
1
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedfortheparameterSSP.(LP2lampislit.)
Wait-function-relatedparametersaredisplayedinorderofthe1stgroup(WT.SW1,WT.TM1,WZ.UP1,Z.LO1),the2ndgroup,the3rdgroup,andsoon.
n
Program Setting Parameter
Menusymbol:( PROG> PTNO.(=01to30)> SEGNO.(=01to99))
Parameter
symbol
Name of
Parameter
Setting Range
Initial
value
User
setting
Display
level
(TSP)
Finaltarget
setpoint
0.0to
100.0%ofPVinputrange(EU)(Setting
range:P.RLtoP.RH)
P.RL
See
"Pro-
gram-
ming"
in
this
manual.
EASY
(TIME)
Segmenttime
setting
-:Unregistered
0.
00to999.59(“hour.minute”or“minute.second”)
*
SettingavailablefortheparameterSEG.T=TIME.
*UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
*If
thesettingis0.00,TSPchangesinstepwise
after one control period.
-
(TM.RT)
Segment
ramp-rate
setting
-:Unregistered
Ramp:
0.0to100.0%ofPVinputrangespan
(EUS)/1houror1minute
Soak:0.00to999.59(“hour.minute”or“minute.second”)
*
SettingavailablefortheparameterSEG.T=TM.RT
*UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
Per1hour:TMU=HH.MM,Per1minute:TMU=MM.SS
*Ifitissetto0.0%oftheinputrangespan,or
thesegmenttime0.00,theprogrammovesto
thenextsegmentafteronecontrolperiod.
-
(S.PID)
SegmentPID
numberselection
1to8
*PIDnumbercanbesetwhentheparameter“ZON=0.”
1
(JC)
Junction code
CONT:Switchingforcontinuation
HOLD:Hold-onswitching(thecontrollerholdstheend-of-
segmentsetpointwhenthesegmentiscompleted,to
performcontrol).
LOCAL:Local-modeswitching(thecontrollerswitchestoa
localsetpointwhenthesegmentiscompleted).
REM:Remote-modeswitching(thecontrollerswitchestoa
remotesetpointwhenthesegmentiscompleted).
W.SW1toW.SW5:Waitduringswitchingbetweensegments.
W.IV1toW.IV5:Waitwithinasegmentinterval.
W.SL1toW.SL5:Segmentswitching(thecontrollerswitches
toalocalsetpointwhenthesegmentiscompletedafter
release.)(5groups)
W.SR1toW.SR5:Segmentswitching(thecontrollerswitches
toaremotesetpointwhenthesegmentiscompleted
afterrelease.)(5groups)
PLK.1toPLK.30:Linkedtopatterns1to30.
INS.:Allowsasegmenttobeaddedtotheendofaspecied
segment.
DEL.:Allows
aspeciedsegmenttobedeleted.
CONT
See
"Pro-
gram-
ming"
in
this
manual.
STD
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedforthe
parameterSSP.(LP2lampislit.)
n
Program Setting Parameter
Menusymbol:( PROG> PTNO.(=1to30)> SEGNO.(=1to99))
Parameter
symbol
Name of
Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(PV.TY1to
PV.TY8)
PVevent-1
to-8
type
OFF:Disable
(Energized)
1:PV
highlimit,2:PVlowlimit,
3:SPhighlimit,4:SPlowlimit,
5:Deviationhighlimit,
6:Deviationlowlimit,
7:Deviationhighandlowlimits,
8:
Deviationwithinhighandlowlimits,
9:TargetSPhighlimit,
10:TargetSPlowlimit,
11:TargetSPdeviationhighlimit,
12:TargetSPdeviationlowlimit,
13:
TargetSPdeviationhighandlowlimits,
14:
TargetSPdeviationwithinhighandlowlimits,
15:OUThighlimit,16:OUTlowlimit,
17:Cooling-sideOUThighlimit,
18:Cooling-sideOUTlowlimit
*Add100for"de-energized".Forexample,
whenthePVhighlimitisde-energized,the
settingis101.
OFF
See
"Pro-
gram-
ming"
in
this
manual.
STD
to
(PV.EV1to
PV.EV8)
PVevent-1
to-8
setpoint
SetadisplayvalueofsetpointofPValarm,SP
alarm,deviationalarm,oroutputalarm.
-19999to30000(Setavaluewithintheinput
range.)
Decimalpoint
positiondependsontheinput
type.
0
to
(TME1to
TME16)
Start condition
of
timeevent1to16
ON:StartONstate
OFF:StartOFFstate
OFF
to
(T.ON1to
T.ON16)
Ontime
oftime
event1to16
-:Unregistered
0.01to999.59(“hour.minute”or“minute.
second”)
*Available
onlywithinthesegmenttime.
*OFFwhentheoperationmodeischanged
tothemodeexcepttheprogramoperation.
*
UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
-
to
(T.OF1to
T.OF16)
Off
timeoftime
event1to16
-
PVevent
andTimeeventareavailableonlyduringtheprogramoperation.
PVeventparametersaredisplayedinorderofPVevent1(PV.TY1,PV.EV1),PVevent2,PVevent3,andsoon.
TimeeventparametersaredisplayedinorderofTimeevent1(TME1,T.ON1,T.OF1),Timeevent2,Timeevent3,
and so on.
n
Local Setting Parameter
Menusymbol: (LOC)
Parameter
symbol
Name of
Parameter
Setting Range
Initial
value
User
setting
Display
level
(LSP)
Localtarget
setpoint
0.0to
100.0%ofPVinputrange(EU)(Setting
range:P.RLtoP.RH)
P.RL
EASY
(L.PID)
PIDnumberse-
lectionfor
local-
mode operation
SetaPIDgroupnumbertouse.
1to8
*
AvailableonlyfortheL.PIDwhenZON=0or5.
*Ifsetto“LocalPIDselection,”localPIDisse-
lectedirrespectiveoftheoperationmodes.
1
to
(L.TY1to
L.TY8)
Localevent-1
to
-8type
OFF:Disable
(Energized)
1:PV
highlimit,2:PVlowlimit,
3:SPhighlimit,4:SPlowlimit,
5:Deviationhighlimit,
6:Deviationlowlimit,
7:Deviationhighandlowlimits,
8:
Deviationwithinhighandlowlimits,
9:TargetSPhighlimit,
10:TargetSPlowlimit,
11:TargetSPdeviationhighlimit,
12:TargetSPdeviationlowlimit,
13:
TargetSPdeviationhighandlowlimits,
14:
TargetSPdeviationwithinhighandlowlimits,
15:OUThighlimit,16:OUTlowlimit,
17:Cooling-sideOUThighlimit,
18:Cooling-sideOUTlowlimit
*Add100for"de-energized".Forexample,
whenthePVhighlimitisde-energized,the
settingis101.
OFF
STD
to
(L.EV1to
L.EV8)
Localevent-1
to
-8setpoint
SetadisplayvalueofsetpointofPValarm,SP
alarm,deviationalarm,oroutputalarm.
-19999to30000(Setavaluewithintheinput
range.)
Decimalpoint
positiondependsontheinputtype
0
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedforthe
parameterLSP.(LP2lampislit.)
LocaleventparametersaredisplayedinorderofLocalevent1(L.TY1,L.EV1),Localevent2,Localevent3,
and so on.
n
Alarm Setpoint Setting Parameter
Menusymbol: (AL)
Parameter
symbol
Name of
Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(A1toA8)
Alarm-1to-8
setpoint
Thesealarmsworkirrespectiveoftheoperation
mode.
Setad
isplayvalueofsetpointofPValarm,SPalarm,
deviationalarm,outputalarm,orvelocityalarm.
-19999to30000(Setavaluewithintheinputrange.)
Decimalpointpositiondependsontheinputtype
0
Table
below
EASY
UsethefollowingtabletorecordSPandalarmsetpoints.
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
An
n
SP-related Setting Parameter
Menusymbol: (SPS)
Parameter
symbol
Name of Parameter Setting Range Initial value
User
setting
Display
level
(RMS)
Remoteinputmethod
RSP:Viaremote(auxiliaryanalog)input
COM:Viacommunication
RSP
STD
(RFL)
Remoteinputlter OFF,1to120s OFF
(RT)
Remoteinputratio
SP=RemoteinputxRT+Re-
moteinput
bias
0.001to9.999
1.000
(RBS)
Remoteinputbias
-100.0to100.0%ofPVinput
rangespan(EUS)
0.0%ofPV
inputrange
span
(SPT)
SPtrackingselection
Trackingisperformedwhenthe
modechangesfromProgramor
RemotetoLocal.(Thelocalset-
pointkeeps
trackoftheprogram
orremotesetpoint.)OFF,ON
OFF
(S.TM)
Startingtimeofprogram
operation
0.00to
999.59(“hour.minute”or
“minute.second”(commonuseof
instrument)
*Use
theparameterTMUtoset
the time unit.
0.00
(PNC)
Programpatternnumber
clearance
OFF:Not
cleared.
ON:Cleared.
(Setthe
programNo.before
restartprogramoperation)
*Thecontrollerresets(clears)
theprogrampatternnumberon
theoperatingdisplayto“0”atthe
endofprogramoperation.
OFF
n
Alarm Function Setting Parameter
Menusymbol: (ALRM)
Parameter
symbol
Name of Parameter Setting Range
Initial
value
User
setting
Display
level
to
(EHY1to
EHY8)
Event-1to
-8hysteresis
ThehysteresissetpointofPVeventor
Localeventissettotheparcentageof0.0
to100.0%.
Thesettingvalue(%)isforthePVinput
rangespanoroutputspan.
0.5 STD
to
(AL1toAL8)
Alarm-1to-8type
Example:Alarm-1
Stand-by
action
Latch action
Energized/
De-energize
Alarm
type
Thesealarmsworkirrespectiveofthe
operation mode.
Seta5-digitvalueinthefollowing
order.
[Alarmtype:
2digits(seebelow)]+
[Without(0)orWith(1)Stand-byac-
tion]+
[Energized(0)orDe-energized
(1)]+[Latchaction(0/1/2/3/4)]
Forlatchaction,seeUser'sManual.
AL1,
AL3:
PVhigh
limit(01)
Without-
Stand-
by
action
(0)
Energi-
zed(0)
Latch
action
(0)
AL2,
AL4:
PVlow
limit(02)
Without
Stand-
by
action
(0)
Energi-
zed(0)
Latch
action
(0)
AL5to
AL8:
not
displayed
for
factory
default
Table
below
EASY
Alarmtype:
2digits
00:Disable
01:
PVhighlimit
02:PVlowlimit
03:SPhighlimit
04:SPlowlimit
05:Deviationhighlimit
06:Deviationlowlimit
07:Deviationhighandlowlimits
08:
Deviationwithinhighandlowlimits
09:TargetSPhighlimit
10:TargetSPlowlimit
11:TargetSPdeviationhighlimit
12:TargetSPdeviationlowlimit
13:
TargetSPdeviationhighandlowlimits
14:TargetSPdeviationwithinhigh
and low limits
15:OUThighlimit
16:OUTlowlimit
17:Cooling-sideOUThighlimit
18:Cooling-sideOUTlowlimit
19:AnaloginputPVhighlimit
20:AnaloginputPVlowlimit
21:AnaloginputRSPhighlimit
22:AnaloginputRSPlowlimit
23:AnaloginputAIN2highlimit
24:AnaloginputAIN2lowlimit
25:AnaloginputAIN4highlimit
26:AnaloginputAIN4lowlimit
27:Feedbackinputhighlimit
28:Feedbackinputlowlimit
29:PVvelocity
30:Faultdiagnosis
31:FAIL
to
(VT1toVT8)
PVvelocityalarmtime
setpoint1to8
0.01to99.59(minute.second) 1.00
to
(HY1toHY8)
Alarm-1to-8hysteresis
Setadisplayvalueofsetpointof
hysteresis.
-19999to
30000(Setavaluewithin
theinputrange.)
Decimalpointpositiondependsonthe
inputtype.Whenthedecimalpointposi-
tionfor
theinputtypeissetto"1",the
initialvalueofthehysteresisis"1.0".
10
to
(DYN1toDYN8)
Alarm-1to-8On-delay
timer
Anal
armoutputisONwhenthedelay
timerexpiresafterthealarmsetpoint
is reached.
0.00to99.59(minute.second)
0.00
STD
(AMD)
Alarmmode
0:Alwaysactive
1:NotactiveinRESETmode
2:NotactiveinRESETorMANmode
0
Forthe
alarmfunctionsettingparameter,4alarmsaredisplayedforthefactorydefault.Thenumberofalarms
canbechangedbythesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,see
User'sManual.
Operation
Guide
Yokogawa Electric Corporation
Parameters
This operation guide describes the functions of parameters briefly. The parameter
symbols listed are in the order shown on the display in each group of menu symbols.
In addition, each parameter table has a “User Setting” column, where you can record
your setpoints when setting them in the controller. The scrolling guide is displayed on
PV display in the Parameter Setting Display. This guide can be turned on/off with
the MODE key.
UP55A
Program Controller
Operation Guide for Single-loop Control

Other manuals for YOKOGAWA UP55A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP55A and is the answer not in the manual?

YOKOGAWA UP55A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP55A
CategoryController
LanguageEnglish

Related product manuals