IM 05P02C41-15EN page 3/14
n
24VDCLoopPowerSupplySpecications
• Use:Powerissuppliedtoa2-wiretransmitter.
• Powersupply:21.6to28.0VDC
• Ratedcurrent:4to20mADC
• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
■ SafetyandEMCStandards
• Safety: Compliant with IEC/EN61010-1 (CE), approved by CAN/CSA C22.2
No.61010-1(CSA),approvedbyUL61010-1.
Installationcategory:CAT.IIPollutiondegree:2
Measurementcategory:I(CAT.I)
Ratedmeasurementinputvoltage:Max.10VDC
Ratedtransientovervoltage:1500V(Note)
Note:ThisisareferencesafetystandardvalueforMeasurementCategoryIofIEC/EN/CSA/
UL61010-1.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.
• EMCConformitystandards:
CEmarking
EN61326-1ClassA,Table2(Foruseinindustriallocations)
EN61326-2-3
EN
55011ClassA,Group1
EN61000-3-2ClassA
EN61000-3-3
C-tickmark
EN55011ClassA,Group1
Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%of
therangeduringtesting.
■ Construction,Installation,andWiring
• Dust-proofand drip-proof: IP56 (for front panel) (Not available forside-by-side
closemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)
• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)
• Weight:0.5kgorless
• Externaldimensions(mm):96(W)×96(H)×65(depthfromthepanelface)
(Depthexcepttheprojectionontherearpanel)
• Installation: Directpanel mounting; mounting bracket, oneeach for upper and
lowermounting
• Panelcutoutdimensions(mm):92
+0.8/0
(W)×92
+0.8/0
(H)
Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.
• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
■ PowerSupplySpecicationsandIsolation
Power supply:
Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz
  24VAC/DC(+10%/-15%)(for/DCoption)
• Powerconsumption:18VA(DC:9VA,AC:14VAif/DCoptionisspecied)
• Databackup:Nonvolatilememory
• Powerholduptime:20ms(for100VACdrive)
• Withstandingvoltage
Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute
Betweenprimaryterminals:1500VACfor1minute
Betweensecondaryterminals:500VACfor1minute
 (Primaryterminals: Power
*
andrelayoutput
terminals;Secondaryterminals:

AnalogI/Osignalterminals,contactinputterminals,communicationterminals

andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.
• Insulationresistance:Betweenpowersupplyterminalsandagrounding terminal
20MΩormoreat500VDC
• Isolationspecications
PV (universal ) input terminals
Remote (universal) input terminals with direct input / Remote input terminals
Aux. analog (AIN2) input terminals
Control relay (contact point c)/Triac output terminals
PV event-1 relay (contact point a) output terminals
PV event-2 relay (contact point a) output terminals
PV event-3 relay (contact point a) output terminals
Position proportional relay output terminals
Contact input terminals (all)
RS-485 communication terminals (2 ports)
Contact output (transistor) terminals
Ethernet communication terminal
PROFIBUS-DP/DeviceNet/CC-Link communication terminals
Current transformer input terminals
Control, retransmission (analog) output terminals
(not isolated between the analog output terminals)
Valve position (feedback) input terminals
Internal
circuits
Power
supply
The circuits divided by lines are insulated mutually.
Aux. analog (AIN4) input terminals
■ EnvironmentalConditions
NormalOperatingConditions:
• Ambienttemperature:-10to50ºC(-10to40ºCforside-by-sideclosemounting)
FortheCC-Linkoption,0to50ºC(0to40ºCforside-by-sideclosemounting)
• Ambienthumidity:20to90%RH(nocondensationallowed)
• Magneticeld:400A/morless
• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90
minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s
2
orless,1oct/minfor90minuteseach
inthethreeaxisdirections
• Short-periodvibration:14.7m/s
2
, 15 seconds or less
• Shock:98m/s
2
or less, 11 ms
• Altitude:2000morlessabovesealevel
• Warm-uptime:30minutesormoreafterthepoweristurnedon
• Startuptime:Within10seconds
*:TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.TheLCDhas
acharacteristicthatthedisplayactionbecomeslateatthelowtemperature.However,the
control fuction is not affected.
TransportationandStorageConditions:
• Temperature:-25to70ºC
• Temperaturechangerate:20ºC/horless
• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions
• Effectofambienttemperature:
VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger
Currentinput:±0.01%ofF.S./ºC
RTDinput:±0.05ºC/ºC(ambienttemperature)orless
Analogoutput:±0.02%ofF.S./ºCorless
• Effectofpowersupplyvoltageuctuation
Analoginput:±0.05%ofF.S.orless
Analogoutput:±0.05%ofF.S.orless
(Eachwithinratedvoltagerange)
5. How to Connect Wires
WARNING
Wiring work must be carried out by a person with basic electrical
knowledge and practical experience.
Be sure to turn OFF the power supply to the controller before wiring
to avoid an electric shock. Use a tester or similar device to ensure
that no power is being supplied to a cable to be connected.
As a safet y me asure, alwa ys insta ll a ci rcuit break er (an IEC
60947-compatible product, 5 A, 100 V or 220 V AC) in an easily
accessible location near the instrument. Moreover, provide indication
that the switch is a device for turning off the power to the instrument.
Install the power cable keeping a distance of more than 1 cm
from other signal wires.
The power cable is required to meet the IEC standards concerned or the
requirements of the area in which the instrument is being installed.
Wiring should be installed to conform to NEC (National Electrical
Code:ANSI/NFPA-70) orthe wiring construction standards in
countries or regions where wiring will be installed.
For control
relay output, alarm relay output, and power terminal
connections, use heat-resistant cables.
Si
nce the insulation provided to each relay output terminal
is Functional insulation, provide Reinforced insulation to the
external of the device as necessary. (Refer to the drawing below.)
This product
Functional
insulation
A safety
voltage circuit
A safety
voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional
insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
A safety
voltage circuit
A safety
voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional
insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
A hazardous
voltage circuit
A hazardous
voltage circuit
CAUTION
When connecting two or more crimp-on terminal lugs to the
single terminal block, bend the crimp-on terminal lugs before
tightening the screw.
Note that
the wiring of two or more crimp-on terminal lugs to the
single high-voltage terminal of the power supply and relay, etc.
does not comply with the safety standard.
CAUTION
Provide electricity from a single-phase power supply. If the
power is noisy, install an isolation transformer on the primary
side, and use a line filter on the secondary side. When measures
against noise are taken, do not install the primary and secondary
power cables close to each other.
If there is a risk of external lightning surges, use a lightning arrester etc.
For TC input, use shielded compensating lead wires for wiring.
For RTD input, use shielded wires that have low conductor
resistance and cause no significant differences in resistance
between the three wires.
Since the
control output relay has a life span (resistance load of
100,000 times), use the auxiliary relay to perform ON/OFF control.
The use
of inductance (L) loads such as auxiliary relays, motors
and solenoid valves causes malfunction or relay failure; always
insert a CR filter for use with alternating current or a diode for
use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
After completing
the wiring, the terminal cover is recommended
to use for the instrument.
● RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
E4-terminal area
E3-terminal area E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101
-112
501
-512
401
-412
301
-312
201
-212
ALM
(Equipped
as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
PV event-2 output
PV event-3 output
PV event-1 output
Common
Common
Common
UP
104
105
106
107
108
109
PV
PV input
TC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equipped
as standard)
202
203
201
202
203
202
203
203
204
Factory default: PV input
type is undefined.
OUT
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
(Suffix code: Output 1; -A or -U)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
-
208
207
208
Can be used for retransmission output or 15 V DC loop power supply when
current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V
DC loop power supply.
RET
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV
retransmission
Load resistance 600 Ω or less
Retransmission output
(Optional suffix code /RT)
205
206
205
206
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
VALV
(Suffix code: Output 1=-P)
Position proportional control output
Resistance: 100 Ω to 2.5 kΩ
Feedback input
100%
0%
Relay contact output
HIGH
(direct)
LOW
(reverse)
COM
Contact rating: 250 V AC, 3A
30 V DC, 3 A
(resistance load)
507
508
509
510
511
512
-
Feedback input
Current (mA)
input
When feedback input is current
510
511
512
+
HBA
(Optional suffix code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
510
511
512
HAL1
HAL2
COM
UP
507
508
509
112
(24 V AC/DC power supply: Optional suffix code /DC)
Power supply
100-240 V AC power supply
N
L
Allowable range:
100-240 V AC (±10%)
(free voltage)
50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
112
112
N
L
OUT
(Suffix code:
Output 1; -T)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
101
102
Triac output
103
NO
COM
Contact rating: 75 - 250 V AC
Allowable load current: 0.8 A
OUT
(Suffix code:
Output 1; -R or -U)
OUT2
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
+
-
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Cooling-side control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A
(resistance load)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
511
512
507
508
509
511
512
511
512
507
508
Triac output
509
NO
COM
Contact rating: 75 - 250 V AC
Allowable load current: 0.8 A
Triac
(Suffix code: Output 2; A or U)
(Suffix code: Output 2; R or U) (Suffix code: Output 2; T)
DI
(Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact
Transistor contact
UP
UP
209
210
211
212
209
210
211
212
Function can be changed.
Start of program operation when
DI1 changes from OFF to ON.
Stop of program operation when
DI2 changes from OFF to ON.
Start of local-mode operation when
DI3 changes from OFF to ON.
Wiring direction
6. Terminal Wiring Diagrams
CAUTION
Do not use an unassigned terminal as the relay terminal.
Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
■ UP55A
Recommendedtighteningtorque:0.6N·m
Applicablewiresize:Powersupplywiring1.25mm
2
or more
Applicable terminal lug Applicable wire size mm
2
(AWG#) (φd) (A) (F)
M3 0.25to
1.65(22to16) 3.3 5.5 4.2
● CableSpecicationsandRecommendedCables
Purpose Name and Manufacturer
Power supply, relay contact outputs 600VGradeheat-resistantPVCinsulatedwires,JISC
3317(HIV),0.9to2.0mm
2
Thermocouple Shieldedcompensatingleadwires,JISC1610
RTD Shieldedwires
(three/fourconductors),UL2482(HitachiCable)
Othersignals(otherthancontactinput/output)
Shielded wires
Othersignals(contactinput/output)
Unshieldedwires
RS-485communication
Shielded wires
Ethernetcommunication
100BASE-TX(CAT-5)/10BASE-T
PROFIBUS-DPcommunication
DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)
DeviceNetcommunication
DedicatedcableforDeviceNet(Shieldedve-wires)
CC-Linkcommunication
DedicatedcableforCC-Link(Shieldedthree-wires)
PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)
DeviceNetConnector(wiringside)(Partnumber:L4502BW)
Recommendedtighteningtorque:0.5to0.6N·m
External DC power supply
Relay
UP’s contact
Diode
(Mount it directly
to the relay coil
terminal (socket).)
Relay
(Use one with a relay coil rating
less than the UP’s contact rating.)
R
UP55A
DC Relay Wiring AC Relay Wiring
UP55A
R
UP’s contact
CR filter
(Mount it directly
to the relay coil
terminal (socket).)
External AC power supply
Relay
(Use one with a relay coil
rating less than the UP’s
contact rating.)