EasyManuals Logo

YOKOGAWA UT320 User Manual

YOKOGAWA UT320
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
<Toc> <3. Operations>
3-11
IM 05D01D02-41E 4th Edition: May 31, 2006-00
Controller Behavior and Control Output Manipulation when the Dead Band
is Positive
The following is an example when the DB parameter is set at 12.4%.
If you hold down the
key with the heating-side output under manipulation (i.e., cooling-
side output C = 0.0%), the heating-side output (H =) decreases. Consequently, both the
heating-side and cooling-side outputs change to 0.0%. If you keep the
key held down
longer, you enter the state of manipulating the cooling-side output, and its value begins to
increase.
Inversely, if you hold down the
key with the cooling-side output under manipulation
(i.e., heating-side output H = 0.0%), the cooling-side output (C =) decreases. Conse-
quently, both the heating-side and cooling-side outputs go to 0.0%. If you keep the
key
held down longer, you enter the state of manipulating the heating-side output, and its value
begins to increase.
Cooling-side
manipulated output
Heating-side
manipulated output
Output (%)
DB=12.4
Dead band:
Operating parameter DB
12.40-12.4
Change in manipulated output when the dead band is positive
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for YOKOGAWA UT320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UT320 and is the answer not in the manual?

YOKOGAWA UT320 Specifications

General IconGeneral
BrandYOKOGAWA
ModelUT320
CategoryController
LanguageEnglish

Related product manuals