<Toc> <3. Operations>
3-11
IM 05D01D02-41E 4th Edition: May 31, 2006-00
Controller Behavior and Control Output Manipulation when the Dead Band
is Positive
The following is an example when the DB parameter is set at 12.4%.
If you hold down the
key with the heating-side output under manipulation (i.e., cooling-
side output C = 0.0%), the heating-side output (H =) decreases. Consequently, both the
heating-side and cooling-side outputs change to 0.0%. If you keep the
key held down
longer, you enter the state of manipulating the cooling-side output, and its value begins to
increase.
Inversely, if you hold down the
key with the cooling-side output under manipulation
(i.e., heating-side output H = 0.0%), the cooling-side output (C =) decreases. Conse-
quently, both the heating-side and cooling-side outputs go to 0.0%. If you keep the
key
held down longer, you enter the state of manipulating the heating-side output, and its value
begins to increase.
Cooling-side
manipulated output
Heating-side
manipulated output
Output (%)
DB=12.4
Dead band:
Operating parameter DB
12.40-12.4
Change in manipulated output when the dead band is positive