SM-18001-rev.1
5-29
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(52) Not Prepared (F0)
(53) Automatic OFF Timer Setting (F1)
ThisfunctionisutilizedtosettheOFFtimerfunctionautomaticallywhentheunitisoperatedbythe
wiredcontroller.DuringtheoperationwiththeautomaticOFFtimersettingfunction,thecancellationof
theOFFtimerandthechangingofthesettingperiodforOFFtimercannotbeperformed.
However,theOFFtimerfunctioniscanceledwhentheunitisstopped.Whentheunitisoperated
againafterstoppage,thesettingperiodforOFFtimerissetbytheoptionalsetting.
ThesettingconditionandthesettingperiodforOFFtimerareshownbelow.
(54) Wired Controller Main-Sub Setting (F2)
Thisfunctionisutilizedwhentwowiredcontrollerareinstalledinonesystem.
Setonewiredcontrollertomain“00”,theotherwiredcontrollertosub“01”.
<ExampleforCIW01>
SettingCondition SettingPeriodforOFFTimer
00 Invalid
01 1 hour
02 2 hours
23 23 hours
24 24 hours
0A 30minutes
0B 90minutes
0C 40minutes
0D 45minutes
0E 50minutes
0F 55minutes
NOTES:
1.Thisfunctionisnotavailablewhentheunitiscontrolledbythecentralizedcontroller,the
remotecontrolconnectingwithCentralControllers.
2.TherangeofsettingperiodforOFFtimerdiffersdependingonthewiredcontrollermodel.