5-34
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
SettingCondition Thermistor(Sensor)
00 InletAirThermistor
01 OutletAirThermistor
02 ThermistorofRemoteControl
03 RemoteSensor
(95) Not Prepared (L3)
(96) Not Prepared (L4)...(forDuctedHighStaticType)
(96) Fan Speed during Energy-Saving Forced Thermo-OFF (L4)...(forDuctedMediumStaticand
SlimType)
Thisfunctionisutilizedtoincreasethefanspeedtopreventthedeteriorationofcomfortduetoforce
thermo-OFFforenergysavingduringcoolingoperation.
(97) Not Prepared (L5)
(98) Not Prepared (L6)
(99) Not Prepared (L7)
(100) Not Prepared (L8)
(101) Auxiliary Heater OFF at Defrost Operation (L9)
Thisfunctionisutilizedtoactivate/deactivateheaterduringdefrostoperationwhenheateroperationis
enabled.
Thesettingconditionsandtheheaterduringdefrostareasfollows:
(102) Not Prepared (LA)
(103) Not Prepared (Lb)
(104) Setting Temperature (P1)
Thisfunctionisutilizedtoprovidesettingtemperatureforevery1
o
F(0.5
o
C)at"00"andevery2
o
F(1
o
C)
at "01".
Controldifferentialofthermistoralsotakethetemperatureforevery1
o
F(0.5
o
C)at"00"andevery2
o
F
(1
o
C)at"01".
(105) Not Prepared (P2)
(106) Thermistor Selection (P3)
Thisfunctionisutilizedtoselectthethermistorwithfunction(107).
SettingCondition AirVolumeDuringForceThermo-OFF
AirowVolume HIGH2 HIGH MED LOW
00(Standard) HIGH2 HIGH MED LOW
01(HiSpeed) HIGH2 HIGH2 HIGH MED
(107) Display of Thermistor Temperature (P4)
Thisfunctionisutilizedtodisplaythetemperatureofthesensorselectedat(106).
(108) Setting Temperature Display during Fan Operation (P5)
Thisfunctionisutilizedtoundisplaythesettingtemperatureduringfanmodeoperation.
(109) ECO Button Operation (P6)
Thisfunctionisprohibiting"ECO"buttonoperationbysettingat"01"
(110) Menu Button Operation (P7)
Thisfunctionisutilizedtoinvalidatethemenubutton.
(111) Not Prepared (P8)
(112) Not Prepared (P9)
(113) Not Prepared (PA)
(114) Not Prepared (Pb)
(115) Not Prepared (PC)
SettingCondition HeaterduringDefrost Fan Operation
00 ON SLOW
01 OFF STOP