SM-18001-rev.1
5-35
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(116) Auxiliary Heater Setting (q1)
Thisfunctionisutilizedtoactivate/deactivateauxiliaryheateroperation.
Whenthisfunctionisvalid,the“auxiliaryheater”signalisoutputfromindoorunitPCBconnector
dependingonindoorandoutdoortemperature.
NOTES:
●“Auxiliaryheater”signaldoesnotoutputduringTestRun.
●Fandelaywillstartfor120secondswhentheunitisturnedOFFfromthewiredcontrollerorduring
defrostoperation(whenoptionalfunctionL9onthewiredcontrollerissetto"01").
●Fandelaywillnotstartwhenanalarmhasoccurred.
●AirowvolumeofindoorunitisrestrictedtoHIGHorHIGH2duringtheauxiliaryheaterONisoutput.
●Incasetheauxiliaryheaterisconnectedandthesettingisenabled,duringfollowinginstancesthe
auxiliaryheateralonewithoutheatpumpmayoperateinheatingmode.
DuringDefrostingOperation
LowAmbientTemperature
(117) Auxiliary Heater ON Compensation (for Auxiliary Heater Setting) (q2)
Thisfunctionisutilizedtochangetheindoortemperatureconditiontoactivateauxiliaryheater.
Thisfunctionisinvalidwhenthefunctionof"AuxiliaryHeaterSetting"isinvalid.
SettingCondition ActualControlTemperature
00(Standard) WiredControllerSettingTemperature(IndicatedValue)-3
o
F(-1.5
o
C)
01 WiredControllerSettingTemperature(IndicatedValue)-3
o
F(-2
o
C)
02 WiredControllerSettingTemperature(IndicatedValue)-4
o
F(-2.5
o
C)
03 WiredControllerSettingTemperature(IndicatedValue)-5
o
F(-3
o
C)
04 WiredControllerSettingTemperature(IndicatedValue)-6
o
F(-3.5
o
C)
05 WiredControllerSettingTemperature(IndicatedValue)-7
o
F(-4
o
C)
06 WiredControllerSettingTemperature(IndicatedValue)-8
o
F(-4.5
o
C)
07 WiredControllerSettingTemperature(IndicatedValue)-9
o
F(-5
o
C)
08 WiredControllerSettingTemperature(IndicatedValue)-1
o
F(-0.5
o
C)
09 WiredControllerSettingTemperature(IndicatedValue)-2
o
F(-1
o
C)
(118) Auxiliary Heater OFF Compensation (for Auxiliary Heater Setting) (q3)
Thisfunctionisutilizedtochangetheindoortemperatureconditiontodeactivateauxiliaryheater.
Thisfunctionisinvalidwhenthefunctionof"AuxiliaryHeaterSetting"isinvalid.
SettingCondition ActualControlTemperature
00(Standard) WiredControllerSettingTemperature(IndicatedValue)
01 WiredControllerSettingTemperature(IndicatedValue)+1
o
F(-0.5
o
C)
(119) Ambient Temperature Restriction Setpoint (for Auxiliary Heater Setting) (q4)
ThisfunctionisutilizedtochangetheoutdoorambienttemperatureconditiontoThermo-OFFand
operatewithauxiliaryheateronly.
Iftheambienttemperatureisbelow(q4),theoperationisforcedthermo-OFF.Withthisfunction,
heatingoperationisperformedonlybytheauxiliaryheater.Thereisnoairconditioneroperation.
Thisfunctionisinvalidwhenthefunctionof"AuxiliaryHeaterSetting"isinvalid.
SettingCondition SettingTemperature(q4)
00(Standard) -4
o
F (-20
o
C)
01 2
o
F (-17
o
C)
02 8
o
F (-13
o
C)
03 14
o
F (-10
o
C)
04 20
o
F (-7
o
C)
05 26
o
F (-3
o
C)
06 32
o
F (0.0
o
C)
07 -13
o
F (-25
o
C)
08 -8
o
F (-22
o
C)
NOTE:
Besuretouseonlythe"00"settingconditionwhencombiningthis"q4"functionwithawatersource
unit.