EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(120) Ambient Temperature Restriction Setpoint Compensation (for Auxiliary Heater Setting) (q5)
Thisfunctionisutilizedtochangetheoutdoorambienttemperatureconditiontochangeoperationfrom
auxiliaryheateronlytoThermo-ONwithauxiliaryheater.
Thisfunctionisinvalidwhenthefunctionof"AuxiliaryHeaterSetting"isinvalid.
SettingCondition ActualControlTemperature
00(Standard) (q4)+4
o
F(2.5
o
C)
01 (q4)+5
o
F(3.0
o
C)
02 (q4)+6
o
F(3.5
o
C)
03 (q4)+1
o
F(0.5
o
C)
04 (q4)+2
o
F(1.0
o
C)
05 (q4)+3
o
F(1.5
o
C)
06 (q4)+3
o
F(2.0
o
C)
(121) Not Prepared (q6)
(122) Not Prepared (q7)
(123) Not Prepared (q8)
(124) Not Prepared (q9)
(125) Not Prepared (qA)
(126) Not Prepared (qb)
(127) Not Prepared (qC)
(128) Not Prepared (qd)
(129) Dual Setpoint (for Automatic COOL/HEAT Operation) (r1)
Thisfunctionisutilizedtoactivate/deactivatedualsetpointofcoolingandheatinginautomaticcooling
andheatingoperation.
Thisfunctionisinvalidwhenthefunctionof"AutomaticCOOL/HEATOperation"isinvalid.
(130) Cooling/Heating Changeover Temperature (for Automatic COOL/HEAT Operation) (r2)
ThisfunctionisutilizedtochangetheindoortemperatureconditiontoThermo-ON/OFF.
Thisfunctionisinvalidwhenthefunctionof"DualSetpoint"isinvalid.
Incasedualsetpointisselectedinautomaticheating/coolingoperation,duringautomodebothcooling
setpointandheatingsetpointcanbeselected.
Bydefault,temperaturewhentheheating/coolingmodechangesareasfollows.
Coolingmodechangestoheatingmodewhentheindoortemperatureisheatingsetpoint-2
o
F(-1
o
C).
Heatingmodechangestocoolingmodewhentheindoortemperatureiscoolingsetpoint+2
o
F(+1
o
C).
SettingCondition ActualControlTemperature
00(Standard) 2
o
F(1.0
o
C)
01 3
o
F(1.5
o
C)
02 3
o
F(2.0
o
C)
03 4
o
F(2.5
o
C)
04 5
o
F(3.0
o
C)
05 1
o
F(0.5
o
C)
NOTE:
Besuretouseonlythe"00"settingconditionwhencombiningthis"q5"functionwithawatersource
unit.