5-36
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(120) Ambient Temperature Restriction Setpoint Compensation (for Auxiliary Heater Setting) (q5)
Thisfunctionisutilizedtochangetheoutdoorambienttemperatureconditiontochangeoperationfrom
auxiliaryheateronlytoThermo-ONwithauxiliaryheater.
Thisfunctionisinvalidwhenthefunctionof"AuxiliaryHeaterSetting"isinvalid.
SettingCondition ActualControlTemperature
00(Standard) (q4)+4
o
F(2.5
o
C)
01 (q4)+5
o
F(3.0
o
C)
02 (q4)+6
o
F(3.5
o
C)
03 (q4)+1
o
F(0.5
o
C)
04 (q4)+2
o
F(1.0
o
C)
05 (q4)+3
o
F(1.5
o
C)
06 (q4)+3
o
F(2.0
o
C)
(121) Not Prepared (q6)
(122) Not Prepared (q7)
(123) Not Prepared (q8)
(124) Not Prepared (q9)
(125) Not Prepared (qA)
(126) Not Prepared (qb)
(127) Not Prepared (qC)
(128) Not Prepared (qd)
(129) Dual Setpoint (for Automatic COOL/HEAT Operation) (r1)
Thisfunctionisutilizedtoactivate/deactivatedualsetpointofcoolingandheatinginautomaticcooling
andheatingoperation.
Thisfunctionisinvalidwhenthefunctionof"AutomaticCOOL/HEATOperation"isinvalid.
(130) Cooling/Heating Changeover Temperature (for Automatic COOL/HEAT Operation) (r2)
ThisfunctionisutilizedtochangetheindoortemperatureconditiontoThermo-ON/OFF.
Thisfunctionisinvalidwhenthefunctionof"DualSetpoint"isinvalid.
Incasedualsetpointisselectedinautomaticheating/coolingoperation,duringautomodebothcooling
setpointandheatingsetpointcanbeselected.
Bydefault,temperaturewhentheheating/coolingmodechangesareasfollows.
Coolingmodechangestoheatingmodewhentheindoortemperatureisheatingsetpoint-2
o
F(-1
o
C).
Heatingmodechangestocoolingmodewhentheindoortemperatureiscoolingsetpoint+2
o
F(+1
o
C).
SettingCondition ActualControlTemperature
00(Standard) 2
o
F(1.0
o
C)
01 3
o
F(1.5
o
C)
02 3
o
F(2.0
o
C)
03 4
o
F(2.5
o
C)
04 5
o
F(3.0
o
C)
05 1
o
F(0.5
o
C)
NOTE:
Besuretouseonlythe"00"settingconditionwhencombiningthis"q5"functionwithawatersource
unit.