OptiView Control Center
Faulty Strong Solution Temp Sensor RT3
This message occurs when the strong solution temper-
ature is less than or equal to 91°F (32.7°C) and the
unit has been running more than 30 minutes. When this
condition occurs the unit closes the alarm contacts.
Recovery Condition
Strong solution temperature is less than 91°F
(32.7°C); releases this warning, it is required to
press the WARNING RESET key in OPERATOR
or SERVICE access to clear the warning.
Pressing the WARNING RESET key at any moment
opens the alarm contacts.
Generator High Pressure > 517mmHg -
Load set to 30%-
This message occurs when the generator shell pressure
is greater than or equal to 517mmHg (10PSIA).
When this warning occurs the unit limits the control
valve opening to 30% and closes the alarm contacts.
Recovery Condition
Generator shell pressure is less than or equal to
310 mmHg (6PSIA), enables control valve opening
greater than 30%, it is required to press the WARN-
ING RESET key in OPERATOR or SERVICE ac-
cess to clear the warning.
Pressing the WARNING RESET key at any moment
will open the alarm contacts.
High Hot Water Supply Temp RT7 > XXX.X°F
(XXX°C)
This message occurs when the unit hot water supply
temperature is greater than or equal to 250°F (121.1°C),
and the unit is congured as hot water low temp. energy
supply. When the units hot water supply temperature is
greater than or equal to 266°F (130°C), and the unit
is congured as hot water high temperature energy
suppy.
Recovery Condition
Hot water supply temperature is less than 249.5°F
(120.8°C), unit is hot water low temp; releases this
warning but it is required to press the WARNING
RESET key in OPERATOR or SERVICE access to
clear the message.
Hot water supply temperature is less than 266°F
(130°C), unit is hot water high temp; releases the
warning, but it is required to press the WARNING
RESET key in OPERATOR or SERVICE access to
clear the message.
Pressing the WARNING RESET key at any moment
opens the alarm contacts.
High Steam supply Press PT2 > 32 PSIA
(220.6KPA)
This message occurs when the units steam supply pres-
sure is greater than or equal to 32PSIA (220.6kPa).
When this condition occurs the unit closes the alarm
contacts.
Recovery Conditions
Steam supply pressure is less than 31 PSIA
(220.6kPa); releases this warning, it is required to
press the WARNING RESET key in OPERATOR
or SERVICE access to clear the message.
Pressing the WARNING RESET key at any moment
will open the alarm contacts.
High Steam Supply Temp RT7 > XXX.X°F
(XXX°C)
This message occurs when the unit Steam supply tem-
perature is greater than or equal to 285°F (140.5°C),
and the unit is congured as steam low temp energy
supply, or when the units Steam supply temperature is
greater than or equal to 337°F (169.4°C), and the unit
is steam high temp energy supply.
Recovery Conditions
Steam supply temperature is less than 284°F
(140°C), unit is steam low temp; releases this warn-
ing but is required to press the WARNING RESET
key in OPERATOR or SERVICE access to clear the
message.
Steam supply temperature is less than 336°F
(168.8°C), unit is steam high temp; releases this
warning but it is required to press the WARNING
RESET key in OPERATOR or SERVICE access to
clear the message.
Pressing the WARNING RESET key at any moment
opens the alarm contacts.