York OPTIVIEW YIA D - Figure 25 - Sample Printout (Setpoints)

York OPTIVIEW YIA D
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
70
FORM 155.21-O1 (615)
Printers
YORK A JOHNSON CONTROLS COMPANY
UNIT MODEL < > SERIAL NUMBER < >
<DATE>, <HOUR>
TOTAL OPERATING HOURS < > [HOURS]
LATEST RUN TIME < > [DAYS, HOURS, MINUTES]
SOFTWARE VERSION < >
- S E T P O I N T S L I S T R E P O R T -
SETPOINT VALUE MIN MAX DEFAULT
LEAVING CHILLED LIQUID TEMP < > 40°F 77°F 44°F
LOW UNLOAD LIMIT < > 10% 20% 10%
MAXIMUM LOAD LIMIT < > 50% 100% 100%
SHORT DILUTION CYCLE < > DISABLE ENABLE ENABLE
AUTOMATIC RESTART AFTER POWER FAILURE < > MANUAL AUTO AUTO
LCHLT RATE LIMIT < > 0.1°F 5.0°F 1.0°F
LCHLT ERROR LIMIT < > 0.1°F 10.0°F 6.0°F
LCHLT MAXIMUM OUTPUT DIFFERENTIAL < > 0.05 0.5 0.2
SSC RATE LIMIT < > 0.10% 2.00% 0.60%
SSC ERROR LIMIT < > 0.10% 2.00% 0.50%
SSC MAXIMUM OUTPUT DIFFERENTIAL < > 0.05 0.5 0.2
SAMPLE FACTOR < > 30SEC 180SEC 60SEC
PERCENT FULL VALVE STROKE < > 50% 130% 100%
PURGE PUMP SERVICE INTERVAL < > 5HRS 100HRS 10HRS
MAXIMUM PURGE/WEEK < > 2 6 4
PURGE PUMP WARM UP TIME < > 2MIN 20MIN 2MIN
LCHLT SHUTDOWN OFFSET < > 2°F 4°F 3°F
RT10 STRONG SOLN FROM STS TEMP OFFSET < > -5°F 5°F 0°F
RT9 CONDENSED REFRIGERANT TEMP OFFSET < > -5°F F 0°F
RT3 STRONG SOLN FROM GEN TEMP OFFSET < > -5°F 5°F 0°F
REFRIGERANT PUMP SHUTOFF DELAY < > 1SEC 45SEC 30SEC
REFRIGERANT PUMP STARTUP DELAY < > 1SEC 900SEC 120SEC
CHILLER REFRIGERANT LEVEL SHUTDOWN DELAY < > 20MIN 60MIN 30MIN
MOTOR COOLANT SOLENOID OPEN TEMP < > 127°F 160°F 160°F
REMOTE LCHLT RESET RANGE < > 10°F 40°F 20°F
PULLDOWN LOADING START SETPOINT < > 10% 30% 10%
PULLDOWN LOADING STOP SETPOINT < > 20% 100% 100%
PULLDOWN INTERVAL TIMER < > 0MIN 255MIN 0MIN
RAMPDOWN INTERVAL TIMER < > 0MIN 60MIN 0MIN
REV. 1.0 2008
FIGURE 25 – SAMPLE PRINTOUT (SETPOINTS)