JOHNSON CONTROLS
60
FORM 155.21-O1 (615)
OptiView Control Center
Generator Hi-Press Digital Switch HP1 Opened
The generator high pressure digital safety switch opened
(Shutdown = 710 mmHg Abs). If the chiller was in RUN
status, the chiller initiates a dilution cycle.
Recovery Conditions
If the chiller was in RUN status at the time of the
event, then when the digital safety contacts close
(Reset = 40 mmHg Abs) and the unit switch is
taken to STOP/RESET position the chiller continues
dilution if it was in progress or becomes ready to
start.
If the chiller was not in RUN status at the time of the
event, when the digital safety contacts close (reset
= 40 mmHg Abs) and the unit switch is placed to
STOP/RESET position the chiller becomes ready
to start.
Gen Hi-Temp Digital Switch HT1 Opened –
Man Reset
The generator high temperature digital safety switch
opened (Shutdown = 337ºF/169ºC). If the chiller was
in RUN status, the chiller initiates a dilution cycle.
Recovery Conditions
If the chiller was in RUN status at the time of the
event, then when the digital safety contacts close
(Reset = 333ºF/167ºC) and the unit switch is taken to
STOP/RESET position the chiller continues dilution
if it was in progress or becomes ready to start.
If the chiller was not in RUN status at the time of
the event, when the digital safety contacts close
(Reset = 333ºF/167ºC) and the unit switch is placed
to STOP/RESET position the chiller becomes ready
to start.
High Concentration in Strong Solution
This shutdown occurs when the strong solution con-
centration is greater than or equal to strong solution
concentration safety shutdown limit (66%). When this
occurs the unit will perform a dilution cycle.
Recovery Condition
Strong solution concentration is less than strong
solution concentration safety shutdown limit and the
unit switch is placed to the STOP/RESET position,
the unit becomes "READY TO START" at restart.
High Hot Water Supply Temp RT7 > %XXX.XX°F
The unit is hot water fed and the hot water temperature
less than or equal to 255°F (123°C) and the generator
conguration is for low temp, or the unit is hot water fed
and the hot water temperature is greater than or equal to
270°F (132°C) and the generator conguration is high
temp. The unit will perform a dilution cycle.
Recovery Conditions
• Hot Water temperature is less than 254°F (123°C)
when the generator conguration is low temp and the
unit switch is placed in the STOP/RESET position.
Hot Water temperature is less than 269°F (131°C)
when the generator conguration is high temp and the
unit switch is placed in the STOP/RESET position.
High Steam Supply Press PT2 > 35psia
(241.3kpa)
This safety shutdown occurs when the steam supply pres-
sure is greater than or equal to 35PSIA (241.3KPA), the
unit will perform a dilution cycle.
Recovery Condition
• Steam supply pressure is greater than or equal to
31PSIA and the unit switch is placed to the STOP/RE-
SET position; unit becomes "READY TO START".
High Steam Supply Temp RT7 > XXX.XX°F
The unit is steam fed and the steam temperature 290°F
(143°C) and the generator conguration is for low temp,
or the unit is steam fed and the steam temperature is
340°F (171°C) and the generator conguration is high
temp. The unit will perform a dilution cycle.
Recovery Conditions
Steam temperature is less than 289°F (142°C) when
the generator conguration is low temp and the unit
switch is placed in the STOP/RESET position.
Steam temperature is less than 339°F (170°C) when
the generator conguration is high temp and the unit
switch is placed in the STOP/RESET position.
Low Refrigerant Temp Analog RT8 < 33ºF
(0.56ºC)
The refrigerant temperature sensed at RT8 is less than or
equal to 33ºF (.56°C). If the chiller was in RUN status,
the chiller will close valves and stop all pumps except
the chilled water pump run contacts.