SECTION 1 - SHIPPING
LOCATION
YORK Chillers are furnished with vibration isola-
tor mounts for basement or ground level installations.
Units may be located on upper floor levels providing
the floor is capable of supporting the total unit operat-
ing weight and optional spring isolators are used. The
chiller should be located in an indoor location where
temperatures range from 40°F to 110°F (4.4°C to
43.3°C).
Sufcient clearance to facilitate normal
service and maintenance work must be
provided all around and above the unit.
Ample space should be provided at either
end to permit cleaning or replacement
of evaporator and condenser tubes – see
Clearance. A doorway or other sufciently
large opening properly located may be
used.
MOTORS
The YD open motor is air cooled. Check state, local
and other codes for ventilation requirements.
FOUNDATION
A level floor, mounting pad or foundation must be pro-
vided by others, capable of supporting the operating
weight of the unit.
CLEARANCE
Clearances should be adhered to as follows:
• Rear and above unit – 2 ft. (61 cm)
• Front of unit – 3 ft. (91 cm)
• Tube Removal – Shell Codes:
B, L, D, H, F, N = 18 ft. (5.5 m) (either end)
M, C, E, K, G = 22 ft. (6.7 m) (either end)
LD09014a
FIGURE 1 - YD FORM 2 RIGGING