SECTION 7 - UNIT CONTROLS
* Refer to Engineering Guide for operation below 30°F (-1.1°C). Alternate thermal expansion valves must be used
below 30°F (-1.1°C).
* When using glycol, Leaving Chilled Liquid Setpoint should not be set below 20°F (-6.7°C).
** Do not exceed 55°F (12.8°C) setpoint before contacting the nearest YORK O󰀩ce for application
guidelines.
TABLE 15 COOLING SETPOINTS, PROGRAMMABLE LIMITS AND DEFAULTS
The line under the 0 is the cursor. If the value is wrong,
it may be changed by using the ↑ (UP) and ↓ (DOWN)
arrow keys until correct. Pressing the ENTER/ADV
key will enter the times and then move the cursor to
the minute box. The operation is then repeated if nec-
essary. This process may be followed until the hour,
minutes, and meridian (AM or PM) of both the START
and STOP points are set. After changing the meridian
of the stop time, pressing the ENTER/ADV key will
advance the schedule to the next day.
Whenever the daily schedule is changed
for Monday, all the other days will
change to the new Monday schedule.
This means if the Monday times are not
applicable for the whole week then the
exceptional days would need to be re-
programmed to the desired schedule.
To page to a specic day, press the SCHEDULE/AD-
VANCE DAY key until the desired day appears. The
start and stop time of each day may be programmed
dierently using the ↑ (UP) and ↓ (DOWN) arrow, and
ENTER/ADV keys.
After SUN (Sunday) schedule appears on the display
a subsequent press of the SCHEDULE/ADVANCE
DAY key will display the Holiday schedule. This is a
two part display. The rst reads:
H O L S T A R T = 0 0 : 0 0 A M
S T O P = 0 0 : 0 0 A M
The times may be set using the same procedure as de-
scribed above for the days of the week. After chang-
ing the meridian of the stop time, pressing the ENTER/
ADV key will advance the schedule to the following
display:
S __ M T W T F S
H O L I D A Y N O T E D B Y *
The line below the empty space next to the S is the
cursor and will move to the next empty space when
the ENTER/ADV key is pressed. To set the Holiday,
the cursor is moved to the space following the day of
the week of the holiday and the (UP) arrow key is
pressed. An * will appear in the space signifying that
day as a holiday. The * can be removed by pressing the
↓ (DOWN) arrow key.
The Holiday schedule must be programmed weekly
–once the Holiday schedule runs, it will revert to the
normal daily schedule.
SETPOINT KEY MODE LOW LIMIT HIGH LIMIT DEFAULT
LEAVING CHILLED LIQUID SETPOINT
WATER COOLING
40.0°F **70.0°F 44.0°F
4.4°C 21.1°C 6.7°C
GLYCOL COOLING
*10.0°F **70.0°F 44.0°F
-12.2°C 21.1°C 6.7°C
LEAVING CHILLED LIQUID
1.5°F 2.5°F 2.0°F
CONTROL RANGE 0.8°C 1.4°C 1.1°C
RETURNED CHILLED LIQUID SETPOINT
WATER COOLING
40.0°F 70.0°F 44.0°F
4.4°C 21.1°C 6.7°C
GLYCOL COOLING
10.0°F 70.0°F 44.0°F
-12.2°C 21.1°C 6.7°C
RETURN CHILLED LIQUID
4.0°F 20.0°F 10.0°F
CONTROL RANGE 2.2°C 11.1°C 5.6°C
MAX EMS-PWM REMOTE
2°F 40°F 20°F
TEMPERATURE RESET 1.0°C 22.0°C 11.0°C