FORM 150.66-NM3
ISSUE DATE: 09/25/2020
149
JOHNSON CONTROLS
SECTION 9 - SERVICE AND TROUBLESHOOTING
9
CHECKING INPUTS AND OUTPUTS
Digital Inputs
Refer to the unit wiring diagram. All digital inputs are
connected to J13 of the microboard. The term “digital”
refers to two states either on or o. As an example,
when the ow switch is closed, 30 volts DC will be
applied to J13, pin 5 (J13-5) of the microboard. If the
ow switch is open, 0 volts DC will then be present at
J13-5.
Pin 1 of J13 is an unregulated 30 VDC source used
to supply the DC voltage to the various user contacts,
unit switch, ow switch, etc. This DC source is fac-
tory wired to CTB1, terminal 13. Any switch or con-
tact used as a digital input would be connected to this
terminal, with the other end connecting to its respec-
tive digital input on the microboard. Any time a switch
or contact is closed, 30 VDC would be applied to that
particular digital input. Any time a switch or contact is
open, 0VDC would be applied to that particular digital
input.
Typically, voltages as high as 34 VDC could be mea-
sured for the DC voltage on the digital inputs. This
voltage is in reference to ground. The unit case should
be sucient as a reference point when measuring digi-
tal input voltages.
Analog Inputs – Temperature
Refer to the unit wiring diagram. Temperature inputs
are connected to the microboard on plug J6. These ana-
log inputs represent varying DC signals corresponding
to varying temperatures. All voltages are in reference
to the unit case (ground). Following are the connec-
tions for the temperature sensing inputs:
Outside Air Sensor
J6-6 = +5 VDC regulated supply to sensor.
J6-9 = VDC input signal to the microboard.
See Table 30 for voltage readings that corre
spond to specic outdoor temperatures.
J6-3 = drain (shield connection = 0 VDC) Return
TABLE 30 – OUTDOOR AIR SENSOR
TEMPERATURE/VOLTAGE/
RESISTANCE CORRELATION
TEMP°F
VOLTAGE
(SIGNAL INPUT
TO RETURN)
TEMP°C
0 0.7 -18
5 0.8 -15
10 0.9 -12
15 1.0 -9
20 1.1 -7
25 1.2 -4
30 1.4 -1
35 1.5 2
40 1.7 4
45 1.8 7
50 2.0 10
55 2.2 13
60 2.3 16
65 2.5 18
70 2.6 21
75 2.8 24
80 2.9 27
85 3.1 29
90 3.2 32
95 3.4 35
100 3.5 38
105 3.6 41
110 3.7 43
115 3.8 46
120 3.9 49
125 4.0 52
130 4.1 54