FORM 150.66-NM3
ISSUE DATE: 09/25/2020
47
JOHNSON CONTROLS
SECTION 6 - TECHNICAL DATA
6
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
Excessive ow will cause damage to
the cooler. Do not exceed maximum
cooler ow. Special care should be
taken when multiple chillers are fed
by a single pump.
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls Oce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls Oce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system.
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
OPERATIONAL LIMITATIONS (SI)
TABLE 5 – TEMPERATURES AND FLOWS (SI)
SI UNITS
YCAL
LEAVING WATER
TEMPERATURE (°DC)
COOLER FLOW (L/S) AIR ON CONDENSER (°C)
MIN MAX MIN MAX MIN MAX
0041 4.4 12.8 2.5 12.6 -17.7 51.7
0045 4.4 12.8 2.5 12.6 -17.7 51.7
0051 4.4 12.8 2.5 12.6 -17.7 51.7
0055 4.4 12.8 3.8 18.9 -17.7 51.7
0061 4.4 12.8 3.8 18.9 -17.7 51.7
0065 4.4 12.8 3.8 18.9 -17.7 51.7
0071 4.4 12.8 3.8 18.9 -17.7 51.7
TABLE 6 – VOLTAGE LIMITATIONS
UNIT POWER MIN. MAX.
380-415/3/50 355 415